User manual
17
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
M.2 M.7 M.8
M.2.1
M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
OUT T
M
+ (G)
Fig. 4.k
CAREL NTC probe connection
:
M.2 M.7 M.8
M.2.1
M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
NTC
NTC
Fig. 4.l
CAREL PROBES AVAILABLE:
room: code DPWC112000
•
air ducts: code DPDC112000 and code DPDC212000•
industrial: DPPC112000 and DPPC212000•
If non-CAREL probes are used, check:
voltage signal: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc, terminal M2.1 (GND: •
M2.2);
current signal: 4 to 20, 0 to 20 mA, terminal M2.4 (GND: M2.6).•
In addition, depending on the type of power supply:
+15 Vdc, terminal M2.3;
•
+ 1 Vdc 135 ohm, terminal M2.4. •
INPUT PROBE CONFIGURATION (pin strip connectors JS5, JS6)
JS5
M.2
JS6
Fig. 4.m (detail of electronic board, in the humidi er electrical
compartment)
pin strip con guration position
0 to 10 Vdc
2 to 10Vdc
0 to 1 Vdc, 4 to 20/0 to
20 mA, NTC probes
JS5 main probe
basic con guration
JS6 limit probe
basic con guration
Important:
to avoid unbalanced control, the earth of the probes or the external
•
control devices must be connected to the earth of the appliance’s
controller.
If ON/OFF terminals are not closed, all the internal and external devices •
managed by the controller will be disabled, with the exception of the
drain pump for emptying the unit after extended periods.
Note: in industrial environments (IEC EN61000-6-2), the cables
leaving the unit must not exceed 30 m in length, except for the
main probe (terminals M2 pin 1-2-3-4-5-6), the remote ON/OFF digital
input (terminal M2 pin 7-8) and cable shields for RS485 communication.
4.4 Alarm contact (M6.1 - M6.3)
Contact available for the remote signalling of one or more alarms.
M.5 M.6
M.6.1
M.6.2
M.6.3
NC
C
NO
F
U
S
E
Fig. 4.n
Electrical speci cations: 250 Vac; Imax: 2 A resistive 2 A inductive.
Note: use clamps on the relay terminal blocks (alarm, utilities) to
prevent the cables from being detached.