User manual

17
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
M.2 M.7 M.8
M.2.1
M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
OUT T
M
+ (G)
Fig. 4.k
CAREL NTC probe connection
:
M.2 M.7 M.8
M.2.1
M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
NTC
NTC
Fig. 4.l
CAREL PROBES AVAILABLE:
room: code DPWC112000
air ducts: code DPDC112000 and code DPDC212000
industrial: DPPC112000 and DPPC212000
If non-CAREL probes are used, check:
voltage signal: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc, terminal M2.1 (GND:
M2.2);
current signal: 4 to 20, 0 to 20 mA, terminal M2.4 (GND: M2.6).
In addition, depending on the type of power supply:
+15 Vdc, terminal M2.3;
+ 1 Vdc 135 ohm, terminal M2.4.
INPUT PROBE CONFIGURATION (pin strip connectors JS5, JS6)
JS5
M.2
JS6
Fig. 4.m (detail of electronic board, in the humidi er electrical
compartment)
pin strip con guration position
0 to 10 Vdc
2 to 10Vdc
0 to 1 Vdc, 4 to 20/0 to
20 mA, NTC probes
JS5 main probe
basic con guration
JS6 limit probe
basic con guration
Important:
to avoid unbalanced control, the earth of the probes or the external
control devices must be connected to the earth of the appliance’s
controller.
If ON/OFF terminals are not closed, all the internal and external devices
managed by the controller will be disabled, with the exception of the
drain pump for emptying the unit after extended periods.
Note: in industrial environments (IEC EN61000-6-2), the cables
leaving the unit must not exceed 30 m in length, except for the
main probe (terminals M2 pin 1-2-3-4-5-6), the remote ON/OFF digital
input (terminal M2 pin 7-8) and cable shields for RS485 communication.
4.4 Alarm contact (M6.1 - M6.3)
Contact available for the remote signalling of one or more alarms.
M.5 M.6
M.6.1
M.6.2
M.6.3
NC
C
NO
F
U
S
E
Fig. 4.n
Electrical speci cations: 250 Vac; Imax: 2 A resistive 2 A inductive.
Note: use clamps on the relay terminal blocks (alarm, utilities) to
prevent the cables from being detached.