3.4 Steam hoses
use CAREL hoses (max. 4 m long, see Models of steam hoses”, page 41).
Rigid pipes may break and cause steam leaks;
avoid the formation of pockets or traps (causes of condensate);
avoid choking the hose due to tight bends or twisting.
fasten the end of the hose to the connectors on the humidi er and the
steam distributor using metal clamps, so that these do not detach due
to the high temperature.
3.5 Condensate drain hose
During the operation of the humidi er some of the steam may condense,
causing a decline in e ciency and noise (gurgling).
To drain the condensate, connect a drain hose with a drain trap and a
minimum slope of 5° to the bottom of the humidi er (see Fig. 3.d). CAREL
condensate drain hoses: code 312353APG
Important:
Important: the drain trap in the condensate drain hose must be
lled with water before starting the humidi er.
Example of correct and incorrect installation of the steam hose and
condensate drain hose.
Final checks
the steam outlet hoses run upwards and the distributor has a
minimum incline of 2° upwards (see Fig. 3.c);
the ends of the hose are tightened to the  ttings with metal clamps;
the curves in the tubing are su ciently wide (radius > 300 mm / 11.8”)
so as to not cause bending or choking;
the steam hose has no pockets or traps for condensate to form;
the paths of the steam and condensate hoses are as described in this
chapter (see Fig. 3.d);
the length of the steam hose is no greater than 4 metres (13.1 feet);
the incline of the steam hose is su cient to allow correct draining of
the condensate (> 20° for the upward sections, > 5° for the downward
sections);
the incline of the condensate hose is at least 5° at every point;
the condensate hose always follows a downwards path and features a
drain trap ( lled with water before starting operation) to avoid steam
being released.
YES
>5°
D> 200mm
>5°
R> 300mm
Hb 2m
YES
>20°
>5°
D>200mm
R>300mm
1
All UE models Models UE25 to UE130
(1) extend the hose inside the humidi er to the bottom tank.
YES
>20°
>5°
D>200mm
R>300mm
1
NO
NO
Models UE001 to UE025
(1): connection with  ll tank
All UE models
Fig. 3.d