“UEX-PLUS” +03U220621 - rel. 1.4 - 04.08.2009
installeruserservice
CAREL reserves the right to modify or change its products without prior notice.
Draining due to a signicant reduction in the request for
production
In the event of a signicant reduction in the request for steam production, the
humidier, rather than wait for the level of water (and thus the production)
to decrease due to the eect of the production itself, performs a drain cycle.
The reduction in the request for steam production is considered signicant
if the current is 33% higher than that relating to the requested level. This
function can be disabled: installer menu > drain options > drain if steam
request drops.
Periodical drain
When using water rich in substances such as humus, lime and impurities,
the eciency and the operation of the humidier may be aected. In
these cases, a periodical drain cycle should be set for the cylinder top avoid
accumulating residues.
To enable the periodical drain: installer menu > drain options > periodic
cylinder ush
To set the drain interval: installer menu > drain options > time interval
14.6 Automatic insucient supply water
management
The humidier checks whether there is no supply water or the ow-rate
of supply water is too low, by measuring if the current at the electrodes
increases after opening the ll solenoid valve.
In this case, the humidier:
• activatesthealarmrelay,
• opensthecontactorandclosesthellsolenoidvalvefor10minutes
After the 10 minutes, the ll solenoid valve is opened, the contactor closed
and the phase current measured: if it increases the alarm is deactivated,
otherwise the procedure is repeated.
NOTE: the alarm is reset automatically and is managed according to the
procedure described above.
14.7 Cylinder “exhaustion” and cylinder “
pre-exhaustion” alarms
To disable the “cylinder exhaustion” alarm: installer menu > options > cylinder
pre-exhaustion alarm
To set “cylinder exhaustion warning” (maximum operating hours): installer
menu > options > cylinder lifetime warning (setting “0” disables the alarm).