User manual

51
ENG
“UEX-PLUS” +03U220621 - rel. 1.4 - 04.08.2009
installeruserservice
10 R humidistat status: 0 = open, 1 = closed
11 R remote on/o status:
0 = open = ue disabled
1 = closed = ue enabled
12 R high conductivity alarm
13 R high conductivity warning
14 R cylinder 1: high current alarm
15 R cylinder 1: low current alarm
16 R cylinder 1: lack of water alarm
17 R cylinder 1: low production alarm
18 R cylinder 1: drain alarm
19 R cylinder 1: full without demand alarm
20 R cylinder 1: maintenance-due alarm (timed)
21 R cylinder 1: pre-exhaustion warning
22 R cylinder 1: foam warning
23 R cylinder 1: totally exhausted warning
24 R cylinder 1: maintenance-due warning (timed)
25 R cylinder 2: high current alarm
26 R cylinder 2: low current alarm
27 R cylinder 2: lack of water alarm
28 R cylinder 2: low production alarm
29 R cylinder 2: drain alarm
30 R cylinder 2: full without demand alarm
31 R cylinder 2: maintenance-due alarm
32 R cylinder 2: pre-exhaustion warning
33 R cylinder 2: foam warning
34 R cylinder 2: totally exhausted warning
35 R cylinder 2: maintenance-due warning
36 R warning: room probe/external regulator not properly connected (only when their signal is 2-10 v or 4-20 ma)
37 R warning: limit probe not properly connected (only when their signal is 2-10 v or 4-20 ma)
38 R room high humidity warning
39 R room low humidity warning
40 R limit probe high humidity warning
41 R hour counter alarm
42 R/W drain for strong demand reduction:
1 = enabled, 0 = disabled
43 R/W long-inactivity drain: 1 = enabled, 0 = disabled
44 R/W total periodical ush: 1 = enabled, 0 = disabled
45 R/W dehumidication: 1 = enabled, 0 = disabled
46 R/W dilution drain with contactor opened: 1 = enabled, 0 = disabled
47 R/W warnings for pre-exhaustion and complete exhaustion: 1 = enabled, 0 = disabled
48 R/W cylinders in parallel or series: 0 = parallel, 1 = series
49 R/W cylinder 1: reset of the hour counter
50 R/W cylinder 2: reset of the hour counter
51 R/W alarms reset
52 R/W cylinder 1: manual drain: 1 = on, 0 = o
53 R/W cylinder 2: manual drain: 1 = on, 0 = o
54 R/W cylinder 1: cleaning cycle: 1 = on, 0 = o
55 R/W cylinder 2: cleaning cycle: 1 = on, 0 = o