Important: the operations described in this menu must only be
carried out by qualied personnel.
From the main screen press:
PRG to access the main menu,
•
DOWN to select the maintenance menu,•
ENTER,•
ENTER, •
UP or DOWN to enter the password “77”,•
ENTER to conrm and access the maintenance menu.•
Maintenance menu screens:
1.Resetconfigurations
2.Systeminfo
3.Manualprocedure
4.Changecylinder
5.Alarmlog
9.1 Reset congurations
Functions:
save the set conguration,
•
recall the saved conguration,•
display the type of humidier,•
install the default parameters for the model of humidier displayed. •
parameter range UOM
saveconfigurationsi
YES/NO
recallconfigurationsi
YES/NO
humidifiertype
xxx Kg/h xxx V x-ph kg/h, V, ph
installdefaultvalues
YES/NO
9.2 System info
Functions:
display the code and version of the application installed;•
change the language;•
display the “select language” screen when the humidier is started.•
parameter display/range
Bios
read-only
Boot
read-only
Code
read-only
Version
read-only
Language
Italian, English, German,
French, Spanish
showlanguagemasktounitstart-up?
YES/NO
9.3 Manual procedure
Important: these operations must only be performed by qualied
personnel, incorrect use may cause serious damage.
These procedures are used to manually test the main functions and
operations of the humidier:
closing of the contactor/contactors•
opening of the water ll valve/valves•
activation of the drain pump/pumps•
alarm relay•
activation of the dehumidier contact•
Manual procedure, cylinder
parameter display/range
manualprocedure
Y/N
powercontactor
ON/OFF
fillvalve
ON/OFF
drainpump
ON/OFF
alarmrelay
ON/OFF
dehumidif.contact
ON/OFF
In the models with two cylinders, there is a second screen for the second
cylinder (with the same functions and procedures as the rst).
9.4 Change cylinder
Complete the following procedure before changing the cylinder:
parameter range
emptycylinder
YES/NO
resetcylinderlifetimecounter
YES/NO
lastreplace(readonly)
dd/mm/yy
flushnewcylinder(*)
YES/NO
(*) wash the new cylinder when replacing.
In the models with two cylinders, there is a second screen for the second
cylinder (with the same functions and procedures as the rst).
9.5 Alarm history
Recorded trace of the alarms (events) that have been activated. The
humidier memory can record up to 200 events (complete with description
and date, press DOWN to scroll the list).
parameter display
Alarm
event description
Time
hh:mm
Date
dd/mm/yy
9. MAINTENANCE MENU