8.6 Supervisor
parameter range def. UOM
identification
numberforBMS
network
0 to 200 1
Com.speed
1200, 2400, 4800, 9600,
19200
19200 Bps
Protocol
CAREL, MODBUS,
LON, RS232, GSM(*),
WINLOAD
CAREL
EnableOn/OFFfrom
supervisor
YES/NO NO
(*)
By setting the GSM protocol, when alarms are activated the humidier
sends an SMS (short message service) to the mobile telephone number set.
1. Important: to send an SMS, the humidier must be tted with
the electronic board code PCO100MDM0, the GSM modem kit
code PLW0PGSM00, and a SIM card in the modem (see par. “GSM
network connection” page 17).
“SMS” conguration procedure
set the GSM protocol from the “Supervisor” screen (see “Supervisor” screen •
> “Protocol”);
press ENTER until the cursor is at the start of the screen;•
press the DOWN button and access the “SMS” screen;•
congure the “SMS” screen:•
SMS
parameter range default
textonmasksendSMS
enter text(*) CAREL HUMISTEAM
mobilenumber
enter mobile phone
number (*)
-
modemstatus(displayonly)
parameter display default
field
percentage of signal -
alarmmodem
NO/YES -
(*) Text characters:
A B C D E F G H I J K L
M N O P Q R S T U V W X
Y Z 0 1 2 3 4 5 6 7 8 9
+ - * : ; , ( ) / # %
Function buttons:
UP or DOWN to select the characters;•
ENTER to save and move the cursor to the next character. •
Important: the humidier only has one communication line (baud
rate and protocol). When enabling SMS messages, a supervisory
network can not be created (and vice-versa).
Important:
only use numeric characters;•
disable the PIN code on the SIM card;•
messages can only be sent in SMS format;•
the SMS messages are subject to the charges and conditions of the SIM •
card network operator.