User manual
25
ENG
“UEX-PLUS” +03U220621 - rel. 1.4 - 04.08.2009
installeruserservice
From the main screen press:
PRG to access the main menu,•
DOWN to select the installer menu,•
ENTER,•
ENTER, •
UP or DOWN to enter the password “77”,•
ENTER to conrm and access the installer menu.•
Installer menu screens:
1.Regulationtype
2.Probeconfiguration
3.Operatingoptions
4.Drainoptions
5.Waterconductivity
6.Supervisor
To navigate inside the screens:
UP or DOWN to change the value (within the options/range),
•
ENTER to conrm and move the cursor to the next value •
ESC to return to the installer menu.•
8.1 Type of control
Setting: type of control, type of signal, unit of measure, and in the models
with two cylinders, choice between “parallel sequence” or “series sequence”.
parameter options/range description
Regulationtype
%rH probe humidity control with main
probe
%rH + limit probe humidity control with main
probe and limit probe
Temperature control temperature control
ON/OFF humidity control with
humidistat
Proportional proportional control with
signal set from external
controller
Proportional + limit proportional control with
signal from external controller
and limit probe
Signaltype(not
visiblewithON/
OFFcontrol)
0/10 V (default)
0/20 mA
4/20 mA
0-135 ohm
135-1000 ohm
NTC
0/1 V
2/10V
Meas.unit
°C-kg/h
°F - lb/hr (default)
Cyl.sequence
forunitswith
twocylinders
parallel (default)
series
8.2 Probe conguration
Set the minimum value, maximum value and oset for the probes used.
parameter parameter range default UOM
Mainprobe
config.(not
accessiblein
ON/OFFcontrol
mode)
Min.scale
0 to (Max.
scale)
0.0 %rH °C/ °F
Max.scale
(Min.scale)
to 250
100.0 %rH °C/ °F
Offset
-10.0 to 10.0 0.0 °C/ °F
Limitprobe
config.
(availableonly
in“%rH+limit
probe”control
mode)
Min.scale 0 to (Max.
scale)
0.0 %rH °C/ °F
Max.scale (Min.
scale)...250
100.0 %rH °C/ °F
Oset -10.0 to 10.0 0.0 °C/ °F
8.3 Operating options
Operating options (1/2)
parameter range default UOM
Selectdataviewonmainmask
important: the options for this parameter
depend on the type of control selected.
% rH % rH
°C-°F
Ampere
Kg-lb/h
hours
uS/cm
% signal
cylinderlifetimewarning
YES/NO YES
cylinderlifetimelimit
0 to 4000 1000 hours
alarmrelaylogic
NO/NC NO
pulsedalarmrelay
YES/NO NO
Operating options (2/2)
parameter range default UM description
Delaybeforepower
OFFatsetpoint
0* to 120 0 s used to delay the stop in
production when there
is no steam request
Dehumidif.control
YES/NO NO
Dehumidif.offset
2.0,...,100.0 10.0 %rH
Dehumidif.
hysteresis
2.0,...,19.9 5.0 %rH
Disablecomplete
emptyingforfoam
YES/NO NO
*: 0= deactivated
8.4 Drain options
Drainage options (1/2)
parameter range default UOM description
Drainifsteam
requestdrops
(quickreg.)
YES/NO YES the humidier empties
a small amount of water
if there is a decrease in
steam request
Power-off
electrodeswhen
draining
YES/NO YES
Drainafter
inactivityYES/
NO
YES/NO YES
Inactivitydays
1 to 199 3 d (days)
Drainage options (2/2)
parameter range default UOM
Dilutiondraintime
50 to 200 100 %
Dilutiondrainfreq.
50 to 200 100 %
Additionalperiodiccylinderfl
YES/NO NO
Timeinterval
1 to 120 24 h (hours)
8.5 Water conductivity
The supply water is normally monitored to avoid levels of high conductivity,
and to determine the time the cylinder takes to reach steady operation.
parameter range def. UOM
override
conductivity
0* to 2000 0 uS/cm
conductivity limits
pre-alarm
(warning)
0 to (alarm value) 1000 uS/cm
alarm
(warning value)
to 2000
1250
*: 0= deactivated
8. INSTALLER MENU