User manual
24
ENG
“UEX-PLUS” +03U220621 - rel. 1.4 - 04.08.2009
installeruserservice
7. USER MENU
From the main screen press:
PRG to access the main menu,•
ENTER to select and access the menu user.•
User menu screens:
1.Alarmthresholds
2.Systemclock
3.Enablescheduler
4.Definetimezones
5.Weeklyscheduler
6.Scheduledsetpoint
7.1 Alarm thresholds
parameter par name. range default UOM
Mainprobealarm
thresholds
Highalarm
0 to 100.0 100.0 %
Lowalarm
0 to 100.0 0.0 %
Limitprobealarm
thresholds
Highalarm
0 to 100.0 100.0 %
Alarmdelay
0 to 999 0 min
7.2 System clock
Used to set the timed activation of the humidier
parameter range
hour/min
0 to 23 / 0 to 59
day
1 to 31
month
1 to 12
year
00 to 99
format
dd/mm/yy - mm/dd/yy
weekday
Sunday to Saturday
7.3 Enable scheduler
Enable control of the time bands and the set points
parameter enable
schedulerOn/Off
YES / NO
variablesetpoint
YES / NO
When the time bands are set, the display shows the symbol
7.4 Setting the time bands
Note: this screen is visible if “scheduler ON/OFF” has been enabled (see
the enable scheduler screen).
Set the intervals for the operation of the humidier over a 24h period (one day):
timeband
ON OFF
P1 P1-1
09:00 13:00
P1-2
14:00 21:00
P2
14:00 21:00
P3
always ON
P4
always OFF
Parameters P1 to P4 can be used set how many times steam production is
enabled/disabled over a 24h period:
P1 Two daily ON time bands
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
0
0
24h
24h
P2
OFF
Z1 Z2
20°C
(68°F)
50°C
(122°F)
30°C
(86°F)
Z3 Z4
OFFON
ON
0 24h
0
(32°F)
24h
OFF
P2 Individual ON time band
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
0
0
24h
24h
P2
OFF
Z1 Z2
20°C
(68°F)
50°C
(122°F)
30°C
(86°F)
Z3 Z4
OFFON
ON
0 24h
0
(32°F)
24h
OFF
P3 Always ON
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
0
0
24h
24h
P2
OFF
Z1 Z2
20°C
(68°F)
50°C
(122°F)
30°C
(86°F)
Z3 Z4
OFFON
ON
0 24h
0
(32°F)
24h
OFF
P4 Always OFF
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
0
0
24h
24h
P2
OFF
Z1 Z2
20°C
(68°F)
50°C
(122°F)
30°C
(86°F)
Z3 Z4
OFFON
ON
0 24h
0
(32°F)
24h
OFF
Fig. 7.1
7.5 Weekly scheduler
Note: this screen is visible if “scheduler ON/OFF” has been enabled (see
the enable scheduler screen).
Set the weekly operation of the humidier, using parameters P1 to P4
(congured in the previous screen)
parameter type of time band
Monday
P1,...,P4
Tuesday
P1,...,P4
Wednesday
P1,...,P4
Thursday
P1,...,P4
Friday
P1,...,P4
Saturday
P1,...,P4
Sunday
P1,...,P4
7.6 Scheduled set points
Note: this screen is visible if “variable set point” has been enabled (see
the enable scheduler screen).
Set dierent levels of set points throughout the day (24h):
parameter
ON SETP.
hours %rH
Z1
00:00 0.0...
Z2
00:00 0.0...
Z3
00:00 0.0...
Z4
00:00 0.0...
Parameters Z1 to Z4 can be used to congure up to four dierent temperature
set points at dierent times of a day (parameters Z1, Z2, Z3, Z4).
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
0
0
24h
24h
P2
OFF
Z1 Z2
20°C
(68°F)
50°C
(122°F)
30°C
(86°F)
Z3 Z4
OFFON
ON
0 24h
0
(32°F)
24h
OFF
Fig. 7.b
By setting the “daily” and “variable set point” time bands, steam production
can be programmed according to the needs of the utility.
Note:
during the “OFF” time band, the humidier is NOT actually o, but rather •
steam production is temporarily disabled, even when setting manually;
the “daily” time bands have priority over the “variable set point” bands. For •
example, setting P4 each Monday (humidier o ), parameters Z1, Z2, Z3,
Z4 (dierent set point values) will not be observed, as the humidier is not
programmed to operate on that day.