“UEX-PLUS” +03U220621 - rel. 1.4 - 04.08.2009
installeruserservice
OFFbySuperv• .: steam production disabled by supervisor;
OFFbySched.:• steam production disabled during a pre-set sheduler;
Remote Off:• isteam production interrupted through the opening of
the “Remote ON/OFF” contact;
OFF by Keyb.:• steam production disabled by keyboard (see “SET”
mask);
ManualProc.:• humidier functions managed manually (maintenance
menu > manual procedure);
Norequest:• humidier on, without steam production request.
Hour counter display UOM
Totalhours
value h
Cylinder1
Operatinghours
value h
Cylinder2
Operatinghours
value h
Timebandsactive
YES/NO
Current
Info cylinder 1 display UOM
Cyl.prod.
value lbs/h
Status
(*)
Activity
cylinder activity (**)
Current
value A
Powercontactor
YES/NO
Fillvalve
YES/NO
Drainpump
YES/NO
Info cylinder 2 display UOM
Cyl.prod.
value lbs/h
Status
(*)
Activity
activity of the cylinder (**)
Current
value A
Powercontactor
YES/NO
Fillvalve
YES/NO
Drainpump
YES/NO
(*) cylinder status:
Off
• : stop steam production (no request or signaling of an alarm)
Softstart• : starting steam production;
Operating• : steady operation steam production;
LowProd• .: low production;
Washing• : cylinder washing in progress.
(**) Activity of the cylinder:
Cyl.Off
• : stop steam production (no request or signaling of an alarm);
Fill• : ll valve operating;
Evaporation• : steam production operating;
Drain• : drain pump operating;
StopbyAl.• : steam production stopped by an alarm;
Inact.Drain• : total drain for inactivity;
Pre-clean• : new cylinder washing in progress;
M.Emptying• : manual drain;
Chk.F.Water• : ll water check (from lack of water cylinder alarm);
PeriodFI:• Periodical drain for dilution.
6.7 “SET” mask
Used to set the main values for the humidier.
To access, press ENTER from the “Main” screen, to move from one value to the
next press UP (next) or DOWN (previous) and ENTER to conrm.
Press ESC repeatedly to return to the “Main” screen.
Parameter range default UOM
Setpoint 0to100
50 %rH
Humidifier AUTO/OFF
AUTO
Max.prod. 20to100
100 %
Prop.band. 2to19.9
5 %rH
Lim.probeset* 0to100
80 %rH
Prop.band* 2to19.9
5 %rH
* visible only if the limit probe is enabled
Manual drain:
• accessthe“SET”screen,
• pressUPandDOWNtogetherfor5seconds
The same procedure can be repeated to stop the drain cycle