“UEX-PLUS” +03U220621 - rel. 1.4 - 04.08.2009
installeruserservice
5. 4 Cascading control of other units
The steam production reached can exceed the maximum capacity of the
master unit by connecting one or more slaves
- Master: UEX unit with analogue output to control the other units
- Slave: UEX/UEY unit that operates based on the analogue control signal
received from the master
- each UEX master unit can control up to 30 UEX slave units or 14 UEY slave
units.
Parameter P0 on each single unit (master or slave) only a ects the production
on that unit.
If the master is disabled by remote contact or serial connection, production
will stop on the slaves.
Some alarms also stop the slaves (see the table of alarms)
GRAPH
100%
20%
V
10
9.5
1
% Production
calculated from probe
or input of UEX
analogic output UEX
up to 14/30 Slave units
UE X-plus
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
Example 1
Master Slave 1
Slave 2
Slave 14/30
P0 = 100%
current production = 100%
P0 = 100%
current production = 100%
P0 = 100%
current production = 100%
P0 = 100%
current production = 100%
up to 14/30 Slave units
UE X-plus
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
Example 2
Master Slave 1
Slave 2
Slave 14/30
P0 = 50%
current production = 50%
P0 = 100%
current production = 100%
P0 = 100%
current production = 100%
P0 = 100%
current production = 100%
Connection between UEX Master and UEX/UEY Slave.
Use shielded cable for the connection.
up to 14/30 Slave units
UE X-plus
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
UEX-plus / UE Y- basic
Example 3
Master Slave 1
Slave 2
Slave 14/30
P0 = 100%
current production = 70%
P0 = 100%
current production = 70%
P0 = 50%
current production = 35%
P0 = 80%
current production = 50%