3.4 Steam hoses
use CAREL hoses (max. 4 m ( max. 13 feet)) long, see “Models of steam •
hoses”, page 47). Rigid pipes may break and cause steam leaks;
avoid the formation of pockets or traps (causes of condensate); •
avoid restricting the hose due to tight bends or twisting.•
fasten the end of the hose to the connectors on the humidier and the •
steam distributor using metal clamps, so that these do not detach due to
the high temperature.
Avoid situations that cause stress on the outlet of the steam cylinder and •
on the distributor pipe (see minimum diameter of curving).
3.5 Condensate drain hose
During the operation of the humidier some of the steam may condense,
causing a decline in eciency and noise (gurgling).
To drain the condensate, connect a drain hose with a drain trap and a
minimum slope of 5° to the bottom of the humidier (see Fig. 3.d). CAREL
condensate drain hoses: code CHOSE00038
Important: the drain trap in the condensate drain hose must be
lled with water before starting the humidier.
Example of correct and incorrect installation of the steam hose and
condensate drain hose.
Final checks
the steam outlet hoses run upwards and the distributor has a minimum o
incline of 2° upwards (see Fig. 3.c);
the ends of the hose are tightened to the ttings with metal clamps; o
the curves in the tubing are suciently wide (radius > 300 mm / 11.8”) so o
as to not cause bending or choking;
the steam hose has no pockets or traps for condensate to form; o
the paths of the steam and condensate hoses are as described in this o
chapter (see Fig. 3.d);
the length of the steam hose is no greater than 4 metres (13.1 feet); o
the incline of the steam hose is sucient to allow correct draining of o
the condensate (> 20° for the upward sections, > 5° for the downward
sections);
the incline of the condensate hose is at least 5° at every point; o
the condensate hose always follows a downwards path and features a o
drain trap (lled with water before starting operation) to avoid steam
being released.
YES
>5°
H≤ 2m (6.6 feet )
>20°
D>200mm (7.9”)
R>300mm ( 11.8”)
All UE models
YES
>20°
>5°
D>200mm (7.9”)
R>300mm ( 11.8”)
Models UE25 to UE130
(1) extend the hose inside the humidier to the bottom tank.
YES
>20°
>5°
D>200mm (7.9”)
R>300mm (11.8”)
Models UE001 to UE025
(1): connection with ll tank
NO
NO
All UE models
Fig. 3.d