User manual

12
GB
Wellness +030220571 - rel. 3.0 - 01.10.2007
installeruserservice
3. STEAM DISTRIBUTION
For the correct delivery of steam, a steam distributor must be used, sized
according to output of the humidi er.
In addition, the distributor must be installed in a part of the steam bath
that is easily reached by the hoses running from the humidi er (see Fig.
3.a as an installation example).
3.1 CAREL jet distributors (SDPOEM00**)
These can be  tted horizontally or vertically (hole facing upwards).
See par. “10.4” page 38 for the models of distributors that are compatible
with the humidi ers.
Assembly instructions (see Fig.3.b):
make a series of holes on the wall according to the distributor drilling
template;
insert the distributor;
fasten the  ange using 4 screws.
Fig. 3.b
Key:
A.
steam inlet
B.
condensate drain
C.
steam outlet.
the dimensions of the hole vary depending on the models of
distributor:
model SDPOEM0000: hole made manually, up to 30 mm in diameter);
model SDPOEM0012: diameter of the hole 12 mm;
model SDPOEM0022: diameter of the hole 22 mm.
D
drilling template
Note: if steam hoses with an inside diameter of 30 mm are used,
remove the 22 mm steam inlet section.
3.2 CAREL linear distributors (DP***DR0)
These can be  tted horizontally. See par. “10.5” page 38 for the models of
distributors that are compatible with the humidi ers.
Assembly instructions (see Fig.3.c):
make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
insert the distributor with the steam holes facing upward;
fasten the  ange using 4 screws.
Fig. 3.a
Fig. 3.c
Key:
1
“L”-shaped mounting support (where featured)
2
ange gasket
3
steam inlet (ØA)
4
condensate drain (ØB)
5
fastening screws (see the instruction sheet supplied with the
distributor)
6
length (depending on the model of distributor, see par. “10.5” page 38)
7
angle (around 2°) for draining the condensate.
8
diameter of the hole on the wall (ØY)
Dimensions in mm
CAREL linear distributors
DP***D22R0 DP***D30R0 DP***D40R0
ØA
22 30 40
ØB
10 10 10
ØY
58 68 89
Ø
35 45 60
X
68 77 99
Tab. 3.a
Important:
Important:
t the distributor at a slight incline (at least 2°, to prevent the return
of condensate);
the “L”-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).
3.3 Steam hose
use CAREL hoses (max. 4 m long, see par. “10.3” page 37). Rigid pipes
may break and cause steam leaks;
avoid the formation of pockets or traps (causes of condensate);
avoid choking the hose due to tight bends or twisting.
fasten the end of the hose to the connectors on the humidi er and the
steam distributor using metal clamps, so that these do not detach due
to the high temperature.
1.
2.