3. STEAM DISTRIBUTION
For the correct delivery of steam, a steam distributor must be used, sized
according to output of the humidi er.
In addition, the distributor must be installed in a part of the steam bath
that is easily reached by the hoses running from the humidi er (see Fig.
3.a as an installation example).
3.1 CAREL jet distributors (SDPOEM00**)
These can be tted horizontally or vertically (hole facing upwards).
See par. “10.4” page 38 for the models of distributors that are compatible
with the humidi ers.
Assembly instructions (see Fig.3.b):
make a series of holes on the wall according to the distributor drilling
template;
insert the distributor;
fasten the ange using 4 screws.
Fig. 3.b
Key:
A.
steam inlet
B.
condensate drain
C.
steam outlet.
the dimensions of the hole vary depending on the models of
distributor:
model SDPOEM0000: hole made manually, up to 30 mm in diameter);
model SDPOEM0012: diameter of the hole 12 mm;
model SDPOEM0022: diameter of the hole 22 mm.
D
drilling template
Note: if steam hoses with an inside diameter of 30 mm are used,
remove the 22 mm steam inlet section.
3.2 CAREL linear distributors (DP***DR0)
These can be tted horizontally. See par. “10.5” page 38 for the models of
distributors that are compatible with the humidi ers.
Assembly instructions (see Fig.3.c):
make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
insert the distributor with the steam holes facing upward;
fasten the ange using 4 screws.
•
•
•
•
•
•
Fig. 3.a
Fig. 3.c
Key:
1
“L”-shaped mounting support (where featured)
2
ange gasket
3
steam inlet (ØA)
4
condensate drain (ØB)
5
fastening screws (see the instruction sheet supplied with the
distributor)
6
length (depending on the model of distributor, see par. “10.5” page 38)
7
angle (around 2°) for draining the condensate.
8
diameter of the hole on the wall (ØY)
Dimensions in mm
CAREL linear distributors
DP***D22R0 DP***D30R0 DP***D40R0
ØA
22 30 40
ØB
10 10 10
ØY
58 68 89
Ø
35 45 60
X
68 77 99
Tab. 3.a
Important:
Important:
t the distributor at a slight incline (at least 2°, to prevent the return
of condensate);
the “L”-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).
3.3 Steam hose
use CAREL hoses (max. 4 m long, see par. “10.3” page 37). Rigid pipes
may break and cause steam leaks;
avoid the formation of pockets or traps (causes of condensate);
avoid choking the hose due to tight bends or twisting.
fasten the end of the hose to the connectors on the humidi er and the
steam distributor using metal clamps, so that these do not detach due
to the high temperature.
1.
2.
•
•
•
•