User manual
10
GB
“Wellness” +030220571 - rel. 3.0 - 01.10.2007
installeruserservice
2. WATER CONNECTIONS
Important: before proceeding, disconnect the power supply.
Models UE001 to UE018 Models UE025 to UE065
Fig. 2.a
Water connections:
o
1.
install a manual valve upstream of the installation (to be able
to cut o the water supply);
o
2.
connect the humidi er to the water supply, and t the lter
supplied (code 98C565P016) to the inlet of the ll solenoid
valve.. On models UE001 to UE0018, use a hose with 3/4’’G
ttings (see par. “10.2 Technical speci cations” page 37,
compatible CAREL hose: code FWH3415000). On models
UE025 to UE065 connect the hose with the non-return valve
supplied (code FWHDCV0000) to prevent the water inside the
humidi er from coming into contact with the mains water;
o
3.
install a mechanical lter to trap any solid impurities (to be
connected downstream of the tap);
o
4
connect a section of non-conductive pipe or hose for draining
(resistant to temperatures of 100 °C and with a minimum
inside diameter of 40 mm);
o
5
prepare a funnel to interrupt continuity in the drain line;
o
6
connect a drain trap to prevent the return of bad odours
(minimum inside diameter 40 mm);
o
7
in models UE025 to UE065: connect a drain hose from the
bottom tank of the humidi er (this can run into the drain
funnel).
Important
Important: when installation is completed, ush the supply hose
for around 30 minutes by piping water directly into the drain,
without sending it into the humidi er. This will eliminate any scale or
processing residues that may block the drain pump and cause foam
when boiling.
Fittings provided for the water connections:
Models UE001 to UE018 Models UE025 to UE065
Key:
A.
supply water inlet
B.
drain water outlet
C.
bottom tank drain water outlet (models UE025
to UE065 only)
Fig. 2.b