7.15 Mechanically draining the water in the
cylinder
Drain due to gravity without activating the humidi er, recommended if:
the humidi er is decommissioned, to empty the cylinder without
switching on the humidi er;
to eliminate the residual water following a drain cycle by pump.
Mechanical drain:
make sure that the humidi er is not powered;
remove the cover (see par. “1.6” page 8);
activate the mechanical device under the cylinder (see part. A Fig.
7.a).
Models UE001 to UE018 Models UE025 to UE065
Fig. 7.a
Other types of drains:
manual (from “ON/OFF quick access” screen, see page 19; and manual
procedure, see par. “7.12” page 25);
automatic (see par. “Automatic water drain“ page 23.
•
•
•
•
•
•
•
alarm meaning and cause solution reset alarm
relay
consequence
Warning: CY
Cylinder
maintenance
recommended
cylinder maintenance recommended perform maintenance and/or replace the cylinder manual
(reset
not
active
signal only
Alarm: Mn
Cylinder
maintenance
mandatory
(cylinder OFF)
cylinder maintenance required Replace the cylinder manual
(reset
counter)
active stop steam
production
Clock board
fault
Clock error
backup battery completely
discharged or general problems with the
clock
Electronic microprocessor controller installed inside the
humidi er electrical compartment
manual not
active
signal only
Alarm: utility
board 1 or 2
utilities board o ine or faulty connect the board
deactivate the utility functions relating to the alarm
signal
-
-
automatic active signal only
Tab. 7.a
Cylinder OFF= the cylinder is not able to produce steam
The alarm button performs a number of actions, depending on how
many times it is pressed.
Action/Pressing
the button
E ect
rst time display the alarm code;
if more than one alarm is active at the same time, the
codes are displayed in sequence by pressing UP or
DOWN.
second time if the cause of the alarm has been resolved, the alarm
is no longer displayed and the corresponding relay is
deactivated (if tted)
third time the cause of the alarm has been resolved, the alarm
is no longer displayed, the corresponding relay is
deactivated and the display shows:
fourth time return to the main screen
Tab. 7.b
7.14 Info-menu
Series of screens that describe the functions and the use of the screens in
the management menu.
Enabling “info-menu” (disabled by default), all access to the submenus
will be preceded by a descriptive screen (to continue navigating, press
ENTER).
Enabling info-menu
From the “utility” submenu press:
ENTER to con rm;
DOWN until displaying the screen with the “enable info?” parameter;
ENTER to move the cursor to the value of the parameter (YES/NO);
UP or DOWN to enable the info-menu function (YES);
ESC repeatedly to return to the “Main” screen;
•
•
•
•
•