7.13 Displaying the alarms
From the alarm log submenu, press ENTER to display the alarms (type of
alarm, date and time)
The humidi er saves up to 200 alarms.
alarm meaning and cause solution reset alarm
relay
consequence
Alarm: EP
Low Production
(cylinder OFF)
excessive reduction in steam production,
or excessive foam in the cylinder.
Perform maintenance on the cylinder manual active stop steam
production
Alarm: EF
Lack of water
(cylinder OFF)
no water in the cylinder check that the supply hose and the internal hoses
are not blocked or choked and that there is su cient
pressure (0.1 to 0.8 MPa, 1 to 8 bars);
check the operation of the ll solenoid valve;
check that the steam outlet is not operating with
excessive backpressure, preventing the ow of water
into the cylinder by gravity;
check that the steam outlet hose is not choked and that
there are no pockets of condensate
1.
2.
3.
4.
automatic
(automatic
water return
procedure)
active stop steam
production
Alarm: Ed
Drain
alarm(Cylinder
OFF)
drain malfunction check the water drain circuits and the correct operation of
the electric drain pump
manual active stop steam
production
Alarm: EL
Low urrent
(Cylinder OFF)
power not available; when the unit is
activated no steam is produced
with the unit o and disconnected from the mains, check
the electrical connections.
manual active stop steam
production
Alarm: EH
High current
(Cylinder OFF)
probable fault in the electrodes or water
temporarily too conductive(especially
when restarting after a short stop)
check the operation of the electric drain pump;
check the seal of the ll solenoid valve when not
energised; drain some of the water and re-start.
1.
2.
manual active stop steam
production
Alarm: EC
High
conductivity
(Cylinder OFF)
high supply water conductivity check the limit threshold set;
switch the unit o and clean the electrodes that
measure of the conductivity of the water; if the problem
persists, change the origin of the supply water or use a
suitable treatment system (partial demineralisation).
Note: the problem is not resolved by softening the supply
water
1.
2.
manual active stop steam
production
Warning: Ec
High
conductivity
pre-alarm: high supply water conductivity check the conductivity of the supply water, if
necessary use a suitable treatment system (partial
demineralisation).
Note: the problem is not resolved by softening the supply
water
1. automatic not
active
signal only
Alarm: E=
High temp.
pre-alarm: high temperature check the operation of the probe and the high temperature
parameter
automatic not
active
signal only
Alarm: E_
Low temp.
pre-alarm: low temperature check the operation of the probe and the low temperature
parameter
automatic not
active
signal only
Alarm: E3
Probe 1 fault or
o ine
1st probe disconnectedor faulty alarm check the connection of the probe, and the type of
probe selected on the: “type of probe” screen (“Maint HW”
submenu)
automatic active stop steam
production
Alarm: E4
Probe 2 fault or
o ine
2nd probe disconnectedor faulty alarm check the connection of the probe, and the type of
probe selected on the: “type of probe” screen (“Maint HW”
submenu)
automatic not
active
stop steam
production
Warning:
EA Foam
cylinder
excessive foam in the cylinder during
boiling
the entrainment of foam is generally due to the presence
of surfactants in the water (lubricants, solvents, detergents,
water treatment agents, softeners) or an excessive
concentration of dissolved salts:
drain the water supply lines;
clean the cylinder make sure a softener is not used (if so,
use another source of water or reduce the softening).
1.
2.
manual not
active
signal only
Warning:
CP Pre-
exhaustion
cylinder
pre-alarm: cylinder being depleted perform maintenance and/or replace the cylinder manual not
active
signal only
Alarm: EU
full cylinder
(cylinder OFF)
cylinder full with unit o with the unit o :
check for any leaks from the ll solenoid valve or the
condensate return from the hose, check that the level
sensors are clean
1.
manual active stop steam
production
Warning: CL
Exhaustion
cylinder
cylinder depleted perform maintenance and/or replace the cylinder manual active stop steam
production