7.10 GSM (send SMS on alarms)
By setting the GSM function, when alarms are activated the humidi er
sends an SMS (short message service) to the mobile phone number
con gured.
Important: to send an SMS, the humidi er must be tted with the
electronic board PCO100MDM0, the GSM modem kit
PLW0PGSM00 and a SIM card inserted in the modem (for installation see
par. “5.2” page 17).
Example of an SMS:
“CAREL SPA STEAM BATH New active alarm Cylinder full 16:15 28/ 6/ 7(*)
CAREL – humiSteam code application ....................... and version .........................”
(*)
Time/date (and format) correspond to the humidi er data
Important: the humidi er only has one data line (baud rate and
protocol). Enabling the SMS function disables the supervisory
network (and vice-versa).
Enabling the SMS function
From the “network” submenu:
ENTER to display the “Supervisor” screen;
ENTER to move the cursor to the “Ident. number for BMS net”
parameter;
UP or DOWN to set the identi er number (*) (default: 1);
ENTER to con rm and move the cursor to the “Baud rate” parameter;
UP or DOWN to set the baud rate (for SMS 9600BPS);
ENTER to con rm and move the cursor to the “Protocol” parameter;
UP or DOWN to select the GSM protocol;
ENTER to con rm;
ESC repeatedly to return to the “Main” screen.
SMS settings
From the “GSM” submenu
ENTER to display the “SMS” screen;
ENTER to move the cursor to the “Text on SMS mask” parameter;
UP or DOWN to set the text (see “Characters and symbols for naming
the essences” page 21);
ENTER to set the mobile phone number (**);
DOWN to move the cursor to the following “SMS” screen, to display the
strength of the GSM signal and the status of the modem;
ESC repeatedly to return to the “Main” screen.
(*)
This parameter can be used to associate an identi er to each humidi er.
This function is required to identify each unit within a supervisory
network.
(**)
Important:
only use numeric characters;
disable the PIN code on the SIM card;
the messages can only be sent in SMS format;
the SMS messages are subject to the fees and conditions of the
operator providing the SIM card.
CAREL declines all responsibility for the failure to send and receive SMS
messages.
7.11 Enable supervisor network
From the “network” submenu:
ENTER to display the “Supervisor” screen;
ENTER to move the cursor to the “Ident. number for BMS net”
parameter;
UP or DOWN to set the identi er for each unit
(*)
;
ENTER to con rm and move the cursor to the “Baud rate” parameter;
UP or DOWN to set the baud rate for the network in question;
ENTER to con rm and move the cursor to the “Protocol” parameter;
UP or DOWN to select the type of protocol;
ENTER to con rm;
ESC repeatedly to return to the “Main” screen.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
(*)
For example, to connect three humidi ers to a supervisory network, an
identi er must be assigned to each unit. The supervisor PC will recognise
the three humidi ers using this number.
ON/OFF from supervisor
To enable the humidi er to be switched ON/OFF from the supervisor,
from the “User” submenu press:
ENTER to con rm;
DOWN until displaying the screen with the “enable supervisory ON/
OFF” parameter;
ENTER to move the cursor to the value of the parameter (YES/NO);
UP or DOWN to enable ON/OFF from the supervisor (YES);
ESC repeatedly to return to the “Main” screen.
7.12 Manual procedures (quali ed personnel
only)
Important: these procedures should only be carried out by
quali ed personnel, improper use may cause serious damage.
These procedures are used to manually test the main functions and the
operation of the humidi er.
To enable the manual procedures, the humidi er must not be producing
steam (steam OFF from “ON/OFF quick access” screen).
Accessing the manual procedures:
From the “Maint HW” screen press:
ENTER to con rm;
DOWN to select the “Man. procedure” screen;
ENTER to con rm and move the cursor to eld the enable the
procedure (YES/NO);
UP or DOWN to enable (YES);
ENTER to con rm and move the cursor to “contactor”;
UP or DOWN to test the contactor (ON) and at the end of the test, UP
or DOWN to disable (OFF). Repeat the same procedure for the other
functions that to be tested (on the three consecutive screens);
at the end of the test return to the rst “Man. procedure” screen and
disable the procedure (from YES to NO). The humidi er will return to
normal operation;
ESC repeatedly to return to the “Main” screen.
Manual procedure functions (distributed over three consecutive
screens):
Contactor Screen 1
Fill
Drain
Alarm
Light
Reset hour count
Supply fan Screen 2
Exhaust fan
Essence 1,2,3
Health
Emptying cylinder
(**)
Screen 3
Pre-cleaning cylinder
(**)
(**)
Humidi er automatically reset at the end of the test.
•
•
•
•
•
•
•
•
•
•
•
•
•