“Wellness” +030220571 - rel. 3.0 - 01.10.2007
installeruserservice
Up to until three essences can be set, and selected from the “ON/OFF
quick access” screen or the “Simple” screen. The display will show the
name or number of the chosen essence.
7.5 Time bands
These are used to switch the humidi er on/o and change the set point
at set times.
Two types of time bands are available:
1. Daily bands (“ON/OFF scheduler” parameters): set how many times to
start/stop steam production over a period of 24h:
2 daily operating periods (parameters P1-1 and P1-2)
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
1 daily operating period (parameter P2)
0 24h
P2
OFF OFFON
Humidi er enabled all day (parameter P3)
0 24h
ON
Humidi er disabled all day (parameter P4)
0 24h
OFF
The operating mode (P1, P2, P3, P4) can be associated with each day of
the week (from Monday to Sunday).
2. “Variable set point” bands (“Temp. scheduler” parameters): four di erent
temperature set points that vary throughout the day (parameters Z1, Z2,
Z3, Z4).
Z1 Z2
20°C
50°C
30°C
Z3 Z4
0 24h
The “daily” and “variable set point” time bands can be programmed to
set steam production according to the requirements of the operator
of the steam bath (e.g. based on closing times) and with a customised
temperature trend (using the 4 set point threshold).
Note:
during the time band without operation (“OFF”), the humidi er is
NOT actually o , but rather steam production is temporarily disabled,
including manually;
the “daily” time bands have priority over the “variable set point”. For
example, setting P4 on Monday (steam bath closed), parameters Z1,
Z2, Z3, Z4 (di erent set point values) will be ignored, because the
humidi er is not programmed to operate on that day.
Setting the daily bands (“ON/OFF scheduler”):
From the “User” submenu press:
ENTER to con rm;
DOWN until displaying the “Scheduler” screen;
ENTER to con rm and move the cursor to the “ON/OFF scheduler”
parameter;
UP or DOWN to enable (YES) the daily bands;
ENTER (twice) to return to the start of the screen;
DOWN to access the “Scheduler” screen: to set the daily band start and
end time (P1-1, P1-2 and P2). Use: ENTER to move the cursor and UP or
DOWN to modify the value;
•
•
•
•
•
•
•
•
•
•
•
•
ENTER until move the cursor to the start of the screen;
DOWN to access the following screen, “Week sch.”: this screen can be
used to assign the type of time band (P1, P2, P3, P4) to each day of the
week. Use ENTER to move the cursor and UP or DOWN to modify the
value;
ESC repeatedly to return to the “Main” screen.
The display shows the
symbol (that ashes when the time bands
are active).
Setting the variable set point bands (“Temp. scheduler”):
From the “User” submenu press:
ENTER to con rm;
DOWN until accessing the “Scheduler” screen;
ENTER (twice) to con rm and move the cursor to “Temp. scheduler”;
UP or DOWN to enable (YES) the “Temp. scheduler” parameter;
ENTER to return to the start of the screen;
DOWN until accessing the “T. setpoint” screen: this screen can be used
to customise up to four set point values per day (Z1, Z2, Z3, Z4). Use
ENTER to move the cursor and UP or DOWN to modify the value;
ESC repeatedly to return to the “Main” screen.
The display shows the
symbol (that ashes when the time bands
are active).
7.6 Fans
The use of the supply and exhaust fans:
guarantee air change;
perform the sanitisation cycles;
create the “mist e ect”.
Enabling the fans
From the “Maint HW” submenu press:
DOWN until accessing the “Fans” screen
ENTER to move the cursor to “supply fan”
UP or DOWN to enable (YES) the supply fan
ENTER to move the cursor to exhaust fan
UP or DOWN to enable (YES) the exhaust fan
ESC repeatedly to return to the “Main” screen
The display shows the
symbol (next to if the fans are on).
Manual fan mode
The manual management of the fans, from the “ON/OFF quick access”
screen, is only available if steam production is disabled (OFF). The manual
activation of the fans during steam production is exclusively controlled
from the management menu.
In this way, the fans can be started using the “ON/OFF quick access” screen
(ENTER from the “Main” screen), stopping steam production (steam OFF).
When steam production is ON they will be stopped automatically.
To switch the fans on and o using the management menu (steam ON),
from the “Fans” submenu press:
ENTER to con rm and access the Supply fan and/or Exhaust fan screen
(depending on the fan enabled);
ENTER to move the cursor to Mode (manual/automatic);
UP or DOWN to set “Manual”;
ENTER to move the cursor to Production (ON/OFF);
UP or DOWN to set “ON”;
ENTER to con rm;
UP or DOWN to repeat the same operation for the other fan (if
enabled);
ESC repeatedly to return to the “Main” screen
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•