User manual

21
GB
Wellness +030220571 - rel. 3.0 - 01.10.2007
installeruserservice
7. MAIN CONFIGURATIONS
7.1 Language
The display terminal can be con gured in: Italian, French, Spanish, English,
German.
To change the language, from the “Main screen press:
PRG;
ENTER;
UP or DOWN to enter the password “77”;
ENTER;
DOWN (3 times) until displaying the “Maintenance” submenu;
ENTER;
DOWN (once) until displaying the “Maint SW submenu;
ENTER;
DOWN (5 times) until displaying “SW Input/output screen;
ENTER (twice) to move the cursor to the parameter “language”;
UP or DOWN to change the language;
ENTER to con rm the language selected and return to the “Main
screen
Note: in the “SW Input/output screen, the unit of measure can
also be selected, °C-kg/h (default) or °F-lbs/hr.
7.2 Date and time
To set the date and time, access the “User submenu and press:
ENTER to display the clock screen;
ENTER to move the cursor to the  rst digit of the hour;
UP or DOWN to modify the  rst digit of the hour;
ENTER con rm and move the cursor to the second digit of the hour;
continue with the UP/DOWN buttons and ENTER to set the minutes,
day (number), month, year, weekday (from Monday to Sunday);
7.3 Temperature probes
The humidi er can manage up to two temperature probes:
with one probe, the value read is shown directly on the display;
with two probes, the values saved are “averaged by the humidi er, and
the result is shown on the display (**).
The Temperature probe screen (“Maint HW submenu) can be
accessed to set the relevance of one probe compared the other in
percentage terms (“weigh probes parameter). In addition, for each
probe the minimum and maximum of the scale and the o set can be
set.
Probe settings
From the
Maint HW
submenu press:
probe 1
ENTER to con rm
DOWN to reach the Temperature probe 1” screen
ENTER to con rm and move the cursor to the “type of probe”
parameter
UP or DOWN to select the type of probe
(*)
probe 2
ENTER to save and move the cursor to enable probe 2”;
UP or DOWN to enable the second probe (YES);
ENTER to move the cursor to “weigh probes
(**)
(UP and DOWN to
modify the weights of the 2 probes and ENTER to save and move
the cursor);
ENTER to return to the start of the screen;
DOWN to access the screen Temperature probe 1”;
ENTER to move the cursor to the min. and max. scale and o set
values (UP and DOWN to modify the value and ENTER to save and
move the cursor);
ESC until displaying the “Main” screen.
(*)
Possible probe con gurations: NTC, 0 to 1 V, 2 to 10 V, 0 to 10 V, 0 to 20
mA, 4 to 20 mA, 0 to 135 ohm, 135 to 1000 ohm
(**)
to achieve a temperature value measured with two probes, the
humidi er carries out the following calculation:
Tm= (Ts1*W1/100) + (Ts2*W2/100)
Tm= temperature shown on the display
Ts1 & Ts2= temperatures read by the two probes
W1 & W2= weights attributed to the two probes, percentage value
(W1+W2=100)
For example, with the following values:
Ts1= 42° W1= 60%
Ts2= 44° W2= 40%
Tm= (42*60/100) + (44*40/100)= 42.8 °C
7.4 Essences
The essences are delivered into the steam bath when the humidi er is
producing steam and the temperature reaches 70% of the set point.
For example: if the set point is 50°C, the essence will be delivered when
the humidi er is producing steam and the temperature measured
exceeds 35°C.
Important: make sure that the external essence pump is correctly
connected.
Enabling the essences
From the “Maint HW submenu press:
ENTER to con rm;
DOWN to select the “Essences” screen (essences 1 and 2);
ENTER to con rm;
UP or DOWN to enable (YES) essence 1;
ENTER to con rm;
UP or DOWN to enable (YES) essence 2;
ENTER to con rm;
DOWN to select the “Essences” screen (essence 3);
ENTER to con rm;
UP or DOWN to enable (YES) output essence 3;
ENTER to con rm;
ESC twice to return to the management menu.
Setting the essence operating times
From the “Essences” submenu press:
ENTER to select the “Essence 1” screen;
ENTER to con rm and move the cursor to the Time ON” parameter;
UP or DOWN to modify the ON seconds for essence 1;
ENTER to con rm and move the cursor to the Time OFF” parameter;
UP or DOWN to modify the OFF seconds for essence 1;
ENTER to con rm and move the cursor to the “name parameter;
UP or DOWN to modify the name of the essence, e.g.: Menthol (*);
repeat the same procedure (ON, OFF times and essence name) for the
other essences enabled;
at the end press ESC repeatedly to return to the “Main” screen.
(*) Characters and symbols available for naming the essences:
ABCDE F GHI J KL
MNOP QR S T UV WX
YZ0123456789
+-*:;,()/#
Function buttons:
UP or DOWN to modify the characters;
ENTER to save and move the cursor to the next character. Up to 10
characters can be used.
Write the names of the essences in the “Installers notes” on page 20.