Periodical drain
When using water rich in substances such as humus and lime, a periodical
drain cycle should be set for the cylinder to avoid accumulating
residues.
To enable the periodical drain, set parameter b1 to 64. In this way, every
24 h the humidi er will drain all the stagnant water in the cylinder, and
the display will show code “dP” (periodical drain). If the periodical drain is
enabled, the number of hours between two periodical drain cycles can
be set using parameter “bE”.
Note:
For the manual drain function, see chap. 6, for the mechanical drain see
paragraph 9.4.
12.5 Automatic insu cient supply water
management
The humidi er checks whether there is no supply water or the ow-rate
of supply water is too low, by controlling if the current at the electrodes
increases after opening the ll solenoid valve.
In this case, the humidi er:
displays alarm “EF” •
activates the alarm relay,•
opens the contactor and closes the ll solenoid valve for 10 minutes.•
After the 10 minutes, the ll solenoid valve is opened, the contactor closed
and the phase current measured: if it increases the alarm is deactivated,
otherwise the procedure is repeated.
NOTE: the alarm is reset automatically and is managed according to the
procedure described above.
12.6 Alarm relay switching
Once the operating hours corresponding to the cylinder maintenance
request have been reached (“CY” alarms), the alarm relay (if there are
no other alarms active) will switch for 10 seconds every 12 hours, until
reaching the “Mn” alarm.
This function is activated using parameter b1 (see paragraph 11.6);
normally disabled
12.7 LEDs on the control board
There are three LEDs tted on the expansion board, located above the
control board (near terminal M15.1):
Fig. 12.b
Key:
LED on
board
Symbol on
display
Meaning
Red
alarm in progress (the type of alarm can be
identi ed based on the type of ashing,
see chap. 8)
Yellow
steam production in progress
(led always on for 100% production, 2
blinkng 20%, 3 blinking 30%, ...)
Green humidi er on
Tab. 12.a