User manual
37
ENG
“UE BASIC” +030220630 - rel. 2.2 - 07.11.2008
11.6 Table of parameter b1
b1 Alarm relay
oscillation
when “CY”
alarm is on
Dilution drain
with contactor
Drain if new request ≤ 2/3
current request (contact
open)
Total drain due to
inactivity
Display of “CL” &
“CP” alarms
Alarm relay activated
if...
Periodical total
drain
DEF. 0
OFF
open YES ON, depending on bF ON alarms in progress OFF
1
ON
open YES ON, depending on bF ON alarms in progress OFF
2
OFF
closed YES ON, depending on bF ON alarms in progress OFF
3
ON
closed YES ON, depending on bF ON alarms in progress OFF
4
OFF
open NO ON, depending on bF ON alarms in progress OFF
5
ON
open NO ON, depending on bF ON alarms in progress OFF
6
OFF
closed NO ON, depending on bF ON alarms in progress OFF
7
ON
closed NO ON, depending on bF ON alarms in progress OFF
8
OFF
open YES OFF ON alarms in progress OFF
9
ON
open YES OFF ON alarms in progress OFF
10
OFF
closed YES OFF ON alarms in progress OFF
11
ON
closed YES OFF ON alarms in progress OFF
12
OFF
open NO OFF ON alarms in progress OFF
13
ON
open NO OFF ON alarms in progress OFF
14
OFF
closed NO OFF ON alarms in progress OFF
15
ON
closed NO OFF ON alarms in progress OFF
16
OFF
open YES ON, depending on bF OFF alarms in progress OFF
17
ON
open YES ON, depending on bF OFF alarms in progress OFF
18
OFF
closed YES ON, depending on bF OFF alarms in progress OFF
19
ON
closed YES ON, depending on bF OFF alarms in progress OFF
20
OFF
open NO ON, depending on bF OFF alarms in progress OFF
21
ON
open NO ON, depending on bF OFF alarms in progress OFF
22
OFF
closed NO ON, depending on bF OFF alarms in progress OFF
23
ON
closed NO ON, depending on bF OFF alarms in progress OFF
24
OFF
open YES OFF OFF alarms in progress OFF
25
ON
open YES OFF OFF alarms in progress OFF
26
OFF
closed YES OFF OFF alarms in progress OFF
27
ON
closed YES OFF OFF alarms in progress OFF
28
OFF
open NO OFF OFF alarms in progress OFF
29
ON
open NO OFF OFF alarms in progress OFF
30
OFF
closed NO OFF OFF alarms in progress OFF
31
ON
closed NO OFF OFF alarms in progress OFF
32
OFF
open YES ON, depending on bF ON no alarms in progress OFF
33
ON
open YES ON, depending on bF ON no alarms in progress OFF
34
OFF
closed YES ON, depending on bF ON no alarms in progress OFF
35
ON
closed YES ON, depending on bF ON no alarms in progress OFF
36
OFF
open NO ON, depending on bF ON no alarms in progress OFF
37
ON
open NO ON, depending on bF ON no alarms in progress OFF
38
OFF
closed NO ON, depending on bF ON no alarms in progress OFF
39
ON
closed NO ON, depending on bF ON no alarms in progress OFF
40
OFF
open YES OFF ON no alarms in progress OFF
41
ON
open YES OFF ON no alarms in progress OFF
42
OFF
closed YES OFF ON no alarms in progress OFF
43
ON
closed YES OFF ON no alarms in progress OFF
44
OFF
open NO OFF ON no alarms in progress OFF
45
ON
open NO OFF ON no alarms in progress OFF
46
OFF
closed NO OFF ON no alarms in progress OFF
47
ON
closed NO OFF ON no alarms in progress OFF
48
OFF
open YES ON, depending on bF OFF no alarms in progress OFF
49
ON
open YES ON, depending on bF OFF no alarms in progress OFF
50
OFF
closed YES ON, depending on bF OFF no alarms in progress OFF
51
ON
closed YES ON, depending on bF OFF no alarms in progress OFF
52
OFF
open NO ON, depending on bF OFF no alarms in progress OFF
53
ON
open NO ON, depending on bF OFF no alarms in progress OFF
54
OFF
closed NO ON, depending on bF OFF no alarms in progress OFF
55
ON
closed NO ON, depending on bF OFF no alarms in progress OFF
56
OFF
open YES OFF OFF no alarms in progress OFF
57
ON
open YES OFF OFF no alarms in progress OFF
58
OFF
closed YES OFF OFF no alarms in progress OFF
59
ON
closed YES OFF OFF no alarms in progress OFF
60
OFF
open NO OFF OFF no alarms in progress OFF
61
ON
open NO OFF OFF no alarms in progress OFF
62
OFF
closed NO OFF OFF no alarms in progress OFF
63
ON
closed NO OFF OFF no alarms in progress OFF
64
OFF
open YES ON, depending on bF ON alarms in progress ON, depending on bE
65
ON
open YES ON, depending on bF ON alarms in progress ON, depending on bE
66
OFF
closed YES ON, depending on bF ON alarms in progress ON, depending on bE
67
ON
closed YES ON, depending on bF ON alarms in progress ON, depending on bE
68
OFF
open NO ON, depending on bF ON alarms in progress ON, depending on bE
69
ON
open NO ON, depending on bF ON alarms in progress ON, depending on bE
70
OFF
closed NO ON, depending on bF ON alarms in progress ON, depending on bE
71
ON
closed NO ON, depending on bF ON alarms in progress ON, depending on bE
72
OFF
open YES OFF ON alarms in progress ON, depending on bE
73
ON
open YES OFF ON alarms in progress ON, depending on bE
74
OFF
closed YES OFF ON alarms in progress ON, depending on bE
75
ON
closed YES OFF ON alarms in progress ON, depending on bE
76
OFF
open NO OFF ON alarms in progress ON, depending on bE
77
ON
open NO OFF ON alarms in progress ON, depending on bE