“UE BASIC” +030220630 - rel. 2.2 - 07.11.2008
6. STARTING AND USER INTERFACE
6.4 Keypad
key function
return to the previous display
UP from the main screen: display the humidi cation values
(current, conductivity,....), see the following paragraph
from the list of parameters: circular navigation of the
parameters and set the values
DOWN from the main screen: display the humidi cation values
(current, conductivity,....)
from the list of parameters: circular navigation of the
parameters and set the values
ENTER
(PRG)
for 2 seconds: access the list of parameters
from the list of parameters: select and con rm (like the
“Enter key on a computer keyboard)
6.5 Main display
The display on the humidi er normally shows the current steam
production (kg/h, basic display).
To display other values, press UP or DOWN and scroll the following list:
input signal (0-100%, or ON/OFF if A0=0)
access alarm log (HYS ) (**)
set maximum steam production (parameter P0) (*)
current (A)
conductivity (S/cm)
cylinder hour counter (h)
To return to the basic display, press ESC.
Parameter C0 (see chap. 7) can be used to change the value of the basic
display (default: current steam production).
(*) To modify the maximum steam output (P0) press:
ENTER (display:
)
UP or DOWN to set the value percentage of production (from 20 to
100%)
ENTER to con rm the new value
Press ESC to return to the main screen
Parameter P0 can also be accessed from the list of parameters (see chap. 7).
(**) To display the alarm log (HYS
) press:
ENTER (the most recent alarm is shown)
UP or DOWN to scroll the list of alarms in chronological order
press ESC to return to the main screen
To delete the list of alarms press UP and DOWN for 5 seconds (inside the
alarm log), when the list has been reset the display will show ‘res’.
6.6 Recalling the manufacturer defaults
From the main screen press ENTER until the password screen is shown:
Enter the password 50
The message dEF is displayed,  ashing
Con rm by pressing ENTER or exit by pressing ESC
If no button is pressed for 30 seconds, the display returns to the main
screen.
6.7 Display software release
1) when switching on the unit to display “rel. x.y “(example rel. 1.2)
2) during operation
a) display: from main screen press ESC and UP
b) via network using integer variable 81. Format = # # #. # “(e.g. 12 =
release 1.2)”.
Before starting the humidi er, check:
water connections: chap. 2. In the event of water leaks do not start the
humidi er before having resolved the problem;
steam distribution: chap. 3 and electrical connections chap. 4 .
6.1 Starting
1
1
0
ON
2
if the cylinder is new, run a pre-wash cycle by pressing ENTER +
DOWN for 5 sec. (the cylinder is  lled and emptied three times,
cleaning the inside walls from impurities).
6.2 Stopping
1
empty the water in the cylinder to avoid stagnation (see paragraph 6.6
“Manually drain the water in the cylinder”).
2
1
0
OFF
6.3 Display
humiSteam
basic
esc
μS/cm
Fig. 6.a
Key:
manually drain the cylinder (see paragraph 6.6)
power supply (green LED)
humidi er operating (yellow LED)
alarm (red LED, not  ashing)
conductivity value
time in seconds
instant current value in Amperes
real hour counter
steam  ow-rate (Imperial system)
steam production as a percentage of rated capacity
steam  ow-rate (international system, default)
parameter programming in progress (parameter setup)
maintenance request (alarm active) or display alarm log (HYS)
3 digits, after 999 the display shows to indicate 1000 (only
three digits plus point - between the  rst and the second
digit- are displayed).
steam production in progress
cylinder  lling in progress
foam in the cylinder
presence water in the cylinder
cylinder water drain in progress