7.13 Displaying the alarms
From the alarm log submenu, press ENTER to display the alarms (type of
alarm, date and time)
The humidi er saves up to 200 alarms.
alarm meaning and cause solution reset alarm
relay
consequence
Alarm: EP
Low Production
(cylinder OFF)
excessive reduction in steam production,
or excessive foam in the cylinder.
Perform maintenance on the cylinder manual active stop steam
production
Alarm: EF
Lack of water
(cylinder OFF)
no water in the cylinder check that the supply hose and the internal 1.
hoses are not blocked or choked and that
there is su cient pressure (0.1 to 0.8 MPa, 1 to
8 bars);
check the operation of the  ll solenoid valve;2.
check that the steam outlet is not operating 3.
with excessive backpressure, preventing the
ow of water into the cylinder by gravity;
check that the steam outlet hose is not choked 4.
and that there are no pockets of condensate
automatic
(automatic water
return procedure)
active stop steam
production
Alarm: Ed
Drain
alarm(Cylinder
OFF)
drain malfunction check the water drain circuits and the correct
operation of the electric drain pump
manual active stop steam
production
Alarm: EL
Low urrent
(Cylinder OFF)
power not available; when the unit is
activated no steam is produced
with the unit o and disconnected from the
mains, check the electrical connections.
manual active stop steam
production
Alarm: EH
High current
(Cylinder OFF)
probable fault in the electrodes or water
temporarily too conductive(especially
when restarting after a short stop)
check the operation of the electric drain pump;1.
check the seal of the  ll solenoid valve when 2.
not energised; drain some of the water and
re-start.
manual active stop steam
production
Alarm: EC
High
conductivity
(Cylinder OFF)
high supply water conductivity check the limit threshold set;1.
switch the unit o and clean the electrodes 2.
that measure of the conductivity of the water;
if the problem persists, change the origin of
the supply water or use a suitable treatment
system (partial demineralisation).
Note: the problem is not resolved by softening
the supply water
manual active stop steam
production
Warning: Ec
High
conductivity
pre-alarm: high supply water conductivity check the conductivity of the supply water, 1.
if necessary use a suitable treatment system
(partial demineralisation).
Note: the problem is not resolved by softening
the supply water
automatic not
active
signal only
Alarm: E=
High temp.
pre-alarm: high temperature check the operation of the probe and the high
temperature parameter
automatic not
active
signal only
Alarm: E_
Low temp.
pre-alarm: low temperature check the operation of the probe and the low
temperature parameter
automatic not
active
signal only
Alarm: E3
Probe 1 fault or
o ine
1st probe disconnectedor faulty alarm check the connection of the probe, and the type
of probe selected on the: “type of probe” screen
(“Maint HW submenu)
automatic active stop steam
production
Alarm: E4
Probe 2 fault or
o ine
2nd probe disconnectedor faulty alarm check the connection of the probe, and the type
of probe selected on the: “type of probe” screen
(“Maint HW submenu)
automatic not
active
stop steam
production
Warning:
EA Foam
cylinder
excessive foam in the cylinder during
boiling
the entrainment of foam is generally due to the
presence of surfactants in the water (lubricants,
solvents, detergents, water treatment agents,
softeners) or an excessive concentration of
dissolved salts:
drain the water supply lines;1.
clean the cylinder make sure a softener is not 2.
used (if so, use another source of water or
reduce the softening).
manual not
active
signal only
Warning:
CP Pre-
exhaustion
cylinder
pre-alarm: cylinder being depleted perform maintenance and/or replace the cylinder manual not
active
signal only
Alarm: EU
full cylinder
(cylinder OFF)
cylinder full with unit o with the unit o :
check for any leaks from the  ll solenoid valve 1.
or the condensate return from the hose, check
that the level sensors are clean
manual active stop steam
production