User manual

17
ENG
Wellness +030220571 - rel. 3.2 - 09.04.2009
installeruserservice
5. REMOTE TERMINAL, GSM MODEM AND SUPERVISORY NETWORK
5.1 Remote display terminal
The display terminal can be detached from the humidi er and moved to
another place.
Depending on the distance required, the following are necessary:
up to 50 metres: 6-wire telephone cable and two ferrites (code
0907858AXX) (see Fig. 5.a);
up to 200 metres: two CAREL TCONN6J000 boards, 6-wire telephone
cables and an AWG20-22 shielded cable with 3 twisted pairs (for the
connection of the two boards, Fig. 5.b).
Note: to  ll the empty space left by the display terminal on the
humidi er, use CAREL kit code HCTREW0000.
Remote connection of the terminal up to max 50 m
J18
humiSteam Wellness
3
2
1
2
Fig. 5.a
Key:
1 telephone cable (up to 50 m distance);
2 two ferrites (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Remote connection of the terminal up to 200 m
J18
humiSteam Wellness
4
2
2
A
J14
1 2 3 1 2 3
J15
B
C
SC
A
J14
1 2 3 1 2 3
J15
B
C
SC
5
3
3
1
Fig. 5.b
Key:
1 telephone cable (up to 0.8 m distance);
2 CAREL TCONN6J000 board;
3 pin strip J14 and J15 in position 1-2 (power supply available on the
telephone connectors A, B and C and screw SC);
4
AWG20-22 shielded cable with 3 twisted pairs to move the display
terminal up to 200 m away. Connection to the TCONN6J00 board:
terminal SC function
0 EARTH (shield)
1 +VRL
2 GND
3 RX/TX-
4 RX/TX+
5 GND
6 +VRL
5 remote display terminal
5.2 GSM network connection (send SMS)
The humidi er can be con gured to send SMS message for alarms and
malfunctions (see par. “7.10”, page 25).
humiSteam Wellness
J19
1
2c
3
MODEM
2a
2d
2b
Fig. 5.c (inside humidi er, electrical compartment)
Key:
1 electronic board PCOI00MDM0 (to be connected to connector J19 on
the humidi er board)
2
CAREL GSM kit PLW0P65M00, made up of:
2.a modem
2.b antenna (with magnetic base)
2.c serial cable
2.d power supply
3 SIM card to be inserted in the modem. Make sure that the access
password (PIN number) is not enabled
5.3 Supervisory network (J19)
The humidi er can be connected to the following optional boards:
optional cards characteristics supported protocols
PCOS004850
used for the direct interface of the
controller to an RS485 network
CAREL, modbus®
Winload
PCO10000F0
used to interface of the controller to
an FTT10 LON network, when suitably
programmed
LON-Echelon
PCO1000WB0 provides BACnet 8802.3 Ethernet,
BACnet/IP and MS/TP connectivity
BACnet
PCO1000BA0 Provides BACnet MS/TP over RS485 BACnet
PCO100MDM0
used for the direct interface of the
controller to an RS232 network with an
external modem
CAREL for remote
connections
M.2 M.7
J19
M.8
Fig. 5.d (detail of the electronic board, humidi er electrical compartment)
Important: for the tLAN and pLAN connections in residential
household (IEC EN 55014-1) and residential (IEC EN 61000-6-3)
environments, use shielded cable (with shield connected to GND). This
warning also applies to the cables leaving the unit.