The following table lists the electrical data relating to the power supply
of the various models and the speci cations of each. Note that some
models may be powered at di erent voltages, obviously with di erent
power input and steam production.
power supply nominal speci cations
model steam
production
(2; 4)
(kg/h)
(lbs/hr)
power
(2)
(kW)
code voltages
(1)
(V - type)
current
(2)
(A)
TAM con guration
(5)
cable
(3)
(mm
2
) /
(AWG)
recommended
External fuses
sizes
(3)
(A / type)
wiring
diagram
(Fig.)
UE003 3,0 / 6.6 2,2 M 460 - 3~ 2,8 13.d 100 1,5 / 16 10 A / fast blow 10.b
UE005 5,0 / 11.0 3,7 M 460 - 3~ 4,7 13.a 100 1,5 / 16 10 A / fast blow 10.b
UE008 8,0 / 17.6 6,0 M 460 - 3~ 7,5 13.a 100 2,5/14 16 A / fast blow 10.b
UE010 10,0 / 22.0 7,5 M 460 - 3~ 9,4 13.a 100 2,5/14 16 A / fast blow 10.b
UE015 15,0 / 33.0 11,2 M 460 - 3~ 14,1 13.a 300 10/8 20 A / fast blow 10.b
UE018 18 / 39.7 13,5 M 460 - 3~ 16,9 13.a 500 6 / 10 32 A / fast blow 10.b
UE025 25 / 55.1 18,7 M 460 - 3~ 23,5 13.c 500 10/8 32A / fast blow 10.c
UE035 35 / 77.2 26,2 M 460 - 3~ 32,9 13.c 500 16 / 6 50 A / fast blow 10.c
UE045 45 / 99.2 33,7 M 460 - 3~ 42,4 13.c 700 16 / 6 60 A / fast blow 10.c
UE065 65 / 143.3 48,7 M 460 - 3~ 61,19 13.b 700 35 / 4 100 A / fast blow 10.d
Tab. 11.a
(1)
tolerance allowed on the rated mains voltage: -15%, +10%;
(2)
tolerance on the rated values: +5%, -10% (EN 60335-1);
(3)
recommended values refer to laying PVC or rubber cables in closed
conduits, 20 m (65.6 feet) long; use the local standards, or whichever is more restrictive,
(4)
rated max instant steam production: the average steam production
may be a ected by external factors, such as: ambient temperature,
water quality, steam distribution system;
(5)
refer to the wiring diagrams to verify
the data are not absolute and if these di er from local standards,
the latter must prevail.
TAM con gurations and connections (transformer for measuring the current)
Important: the con gurations and connections are already made by CAREL, and no changes are required. The following diagrams represent possible
connection modes and may be useful in the event of serious electrical malfunctions on the humidi er.
All operations must only be performed by quali ed personnel, improper use may cause serious damage.
one cable turn one turn of the two
cables of the same phase
two cable turns of the
same phase
one cable in double
turn mode
three cable turns of the
same phase
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
Fig. 11.a Fig. 11.b Fig.11.c Fig.11.d Fig.11.e
Important: to avoid interference, separate the power cables
from the probe cables.