Please Note
Please read these instructions in conjunction with the
parameter list.
It is recommended that the controllers be programmed before
connecting or activating the plant to be controlled
(eg compressors)
** If the controller is keypad locked the value will not change.
See parameter C50
Set Point(s)
PRESS “SEL” & HOLD For
1 Second
“ST1”will be displayed
On releasing the button “SET POINT 1”
value will be displayed
PRESS ARROW “UP” or “DOWN” to
set the desired value. **
PRESS “SEL” to confirm the value
If there is only 1 set point then the controller
will then display the measured variable
(eg room temperature).
If the Controller has been programmed for
more than 1 set point (see C0) then “ST2”
will be displayed.
PRESS ARROW “UP” or
“DOWN” to set the desired value for
set point 2
PRESS “SEL” to confirm the value
Common Parameters (P & C0)
PRESS & HOLD “PRG” & “SEL” for
approx 5 seconds
“0” will be displayed
PRESS “ARROW UP” to enter the
password value “22”
PRESS “SEL” to confirm
“C0” will be displayed
A) PRESS “ARROW UP” or
“DOWN” to select the code for the
parameter to be changed.
eg P1 = differential
B) PRESS “SEL”
The Value Set for this parameter
will be displayed
C) PRESS “ARROW UP” or
“DOWN” to set the desired value.
D) PRESS “SEL” to confirm the
value
REPEAT A-D Until all desired
parameters have been set.
PRESS “PRG” To Confirm all
Changes (This is very Important)
All Parameters
As above but enter password “77”
CAREL PROGRAMMING SHEETS
IR32 UNIVERSAL SERIES IR32 / IRDR V, W, Z, A, D PROGRAMMING INSTRUCTIONS