CAREL PROGRAMMING SHEETS
IR32 UNIVERSAL SERIES IR32 / IRDR V, W, Z, A, D PROGRAMMING INSTRUCTIONS
CONTROL PARAMETERS
CODE
MIN
MAX
UNIT
DEF
C0
Operating Mode (ie heating, cooling, heat pump etc)
C0=1 All outputs direct logic eg cooling
C0=2 All outputs reverse logic eg heating (default)
C0=3 1/2 outputs direct 1/2 reverse eg 2 Heat / 2 Cool
C0=5 Alarm Mode,C0=4,6 - 9 Refer operating instructions
22
1
9
2
P1
Differential 1 (When C0= 1,2,3,4,5,6,7,8,9)
22
0.1
99.9
2
P2
Differential 2 (only when C0= 3,4,5,6,7,8,9 or C33=1)
22
0.1
99.9
2
P3
Dead band (only when C0= 3,4, or 5)
22
0
99.9
2
C4
Compensation Coefficient. (NTC models) Refer manual
77
-2.0
2.0
0.5
C5
Control Action 0= Proportional 1= Proportional + Integral
77
0
1
0
C6
Delay between stages starting
77
0
999
sec.
5
C7
Minimum time between starts of the same output
77
0
15
min
0
C8
Minimum off time for each output
77
0
15
min
0
C9
Minimum on time for each output
77
0
15
min
0
C10
Status of the outputs with probe alarm 0=All OFF,
1= All ON, 2= Cool on Heat off, 3=Cool off heat on
77
0
3
0
C11
Rotation 0=No rotation,1 =Stand rotation (all comps),
2= 2+2 Rotation (2 comps 2 valves-energise valve to increase
capacity), 3=2+2 Rotation (2 comps 2 valves-energise valve to
reduce capacity),4 = only rotate output 3 & 4, 5 = only rotate
outputs 1&2, 6 = rotate as pairs (1&2) & (3&4), 7 =rotate outputs
2,3 & 4 (not 1)
77
0
7
0
C12
PWM Cycle time
77
0.2
999
sec
20
C13
Type of sensor -depends on probe input type,refer manual
77
0
1
0
P14
Probe Calibration (offset)
22
-99
+99.9
0
C15
Minimum scaling on analogue inputs (to match sensor)
77
-99
C16
0
C16
Maximum scaling on analogue inputs (to match sensor)
77
C15
999
100
C17
Sensor response
77
1
14
5
C18
Temperature measurement units 0= deg C, 1= deg F
77
0
1
0
C19
Second NTC sensor (only on NTC models) 0= display only of
2nd probe (press arrow down), 1= Differenial Mode
(P1-P2), 2,3,4= Compensation (refer user guide)
77
0
4
0
C21
Set Point 1 min value (range locking)
77
-99
C22
C22
Set Point 1 max value (range locking)
77
C21
999
C23
Set Point 2 min value (range lock),(only when C0=6,7,8,9)
77
-99
C24
C24
Set Point 2 max value (range lock),(only when C0=6,7,8,9)
77
C23
999
P25
Low alarm (absolute value)
22
-99
P26
P26
High alarm (absolute value)
22
P25
999
P27
Alarm differential
22
0.1
99.9
2.0
P28
Alarm time delay
22
0
120
min
60
C29
Digital input 1 config, 0=not used, 1=Immediate external alarm
auto reset, 2=Immediate external alarm manual reset,
3=Delayed external alarm(P28), 4=remote on/off
77
0
4
0
C30
Digital input 2 conf (only IRDR models)settings as per C29
77
0
4
0
C31
Status of outputs with digital input alarm. As per C10
77
0
3
0
C32
Serial address (when connected to network)
77
1
16
1
C33
Do not change- Refer user guide (relates also to C34-C49)
77
0
1
0
C50
Keypad / IR remote locking. 0= KEYPAD - locked set point and
P parameters, IR REMOTE- locked C enabled Set point and P
parameters ,1= KEYPAD-unlocked,REMOTE-locked C enabled
Set point and P parameters,
2=KEYPAD-locked set point and P parameters, REMOTE-
locked,3=KEYPAD-unlocked, REMOTE-locked,
4= KEYPAD and REMOTE unlocked.
77
0
4
4
C51
Code for IR remote - use when more than one controller is close
77
0
120