CAREL PROGRAMMING SHEETS
PJ32 UNIVERSAL PROGRAMMING INSTRUCTIONS
Please Note
Please read these instructions in conjunction with the parameter list.
It is recommended that the controllers be programmed before connecting or activating the plant to be controlled
(eg compressors)
** If the controller is keypad locked the value will not change. See parameter H3
Set Point
PRESS “SET” & HOLD For 1 Second
“SET POINT” Value will be displayed
PRESS ARROW “UP” & “DOWN” to set the
desired value. **
PRESS “SET” to confirm the value
Frequent (F) Parameters
PRESS & HOLD “SET” for approx 5 seconds
“PS ” will be displayed
A) PRESS “ARROW UP” & “DOWN” to select the
parameter to be changed.
eg rd = differential
B) PRESS “SET”
The Value Set for this parameter will be displayed
C) PRESS ARROW “UP” & “DOWN” to set the
desired value.**
D) PRESS “SET” to confirm the value
REPEAT A-D Until all desired parameters have
been set.
PRESS & HOLD “SET” until temp is displayed
(approx 5 seconds) to confirm all changes
(This is very important)
All Parameters
PRESS & HOLD “SET” for approx 5 seconds
“PS” will be displayed
PRESS “SET“ then “ARROW UP” to
until the password value “22” is displayed
PRESS “SET” to confirm
“PS” will be displayed
A) PRESS “ARROW UP” & “DOWN” to select the
code the parameter to be changed.
eg rd = differential
B) PRESS “SET”
The Value Set for this parameter will be displayed
C) PRESS “ARROW UP” & “DOWN” to set the
desired value.
D) PRESS “SEL” to confirm the value
REPEAT A-D Until all desired parameters have
been set.
PRESS & HOLD “SET” until temp is displayed
(approx 5 seconds) to confirm all changes