CAREL PROGRAMMING SHEETS
PJ32 UNIVERSAL PARAMETER SUMMARY
PROBE PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
/2
Measurement stability
C
1
15
-
6
/4
Probe to be displayed (0= sensor 1, 1 = sensor 2
F
0
1
-
0
/5
C/ F (0 = C, 1 = F)
C
0
1
-
0
/6
Display temperature of sensor 2
F
-
-
C/ F
-
/C
Calibration (tenths of degree without decimal pt) i.e. 2=+0.2 C offset
F
-127
+127
C/ F
0.0
DIFFERENTIAL PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
P1
Controller 1 differential (0 = 0.5 C)
F
0
+19
C/ F
3
P2
Controller 2 differential (0 = 0.5 C)
F
0
+19
C/ F
3
CONTROL PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
r1
Controller 1 mode (0 = Direct / 1 = Reverse)
C
0
1
-
0
r2
Controller 2 mode (0 = Direct / 1 = Reverse)
C
0
1
-
0
r3
Minimum set point allowed
C
-50
r4
C/ F
-50
r4
Maximum set point allowed
C
r3
+150
C/ F
60
r5
Controller 2 sensor (0 = sensor 1, 1 = sensor 2)
C
0
1
-
0
CONTROL TIMINGS
TYPE
MIN
MAX
UNIT
DEF
c0
Delay on output energisation at power up
C
0
199
sec
0
c1
Minimum on time for control outputs
C
0
15
min
0
c2
Minimum off time for control outputs
C
0
15
min
0
c3
Interlock outputs (0=no, 1 = yes)
C
0
1
-
0
c4
Minimum time between activation of two different outputs
C
0
199
sec
0
ALARM PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
A0
Alarm differential (0 = 0.5 deg diff)
C
0
+19
C/ F
0
AL
Low temperature alarm (absolute value)
F
-50
AH
C/ F
-50
AH
High temperature alarm (absolute value)
F
AL
+150
C/ F
150
At
Temperature alarm delay
C
0
199
min
0
Ad
External alarm delay (when digital input is used)
C
0
15
min
0
DIGITAL INPUT PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
dI
Digital input operating mode
0 = not used, 1 = Alarm (wired normally closed. Open = Alarm)
2 = change set point
C
0
1
flag
0
OTHER PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
H0
DO NOT CHANGE
C
0
199
-
1
H1
Alarm output status (0 = relay energised with no alarm)
C
0
1
-
0
H2
Output 2 mode (only for 2 relay models) (0 = alarm, 1 = control)
C
0
1
-
1
H3
Disable keypad (0 = disabled)
C
0
1
-
1
H4
Disable buzzer (model specific)
C
0
1
-
0
H5
Identification code for programming key
C
-99
99
-
-