CAREL PROGRAMMING SHEETS
PJ32C REFRIGERATION PARAMETER SUMMARY
PROBE PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
/C
Calibration
F
-127
+127
C/ F
0.0
/2
Measurement stability
C
1
15
-
4
/4
Probe to be displayed (0= control probe, 1 = food probe (second
probe))
C
0
100
0
/5
C/ F (0 = C, 1 = F)
C
0
1
flag
0
CONTROL PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
rd
Control differential ( 0 = 0.5 deg C differential )
F
0
+19
C/ F
2
r1
Minimum set point allowed
C
-50
r2
C/ F
-50
r2
Maximum set point allowed
C
r1
+127
C/ F
60
r3
Enable defrost end on time alarm (Ed)
C
0
1
flag
0
r4
Value to change set point by when A4 (digital input) = 4
C
-20
+20
C/ F
3
COMPRESSOR PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
c0
Compressor start-up delay after power up
C
0
15
min
0
c1
Minimum interval between two compressor starts
C
0
15
min
0
c2
Minimum compressor off-time
C
0
15
min
0
c3
Minimum compressor on-time
C
0
15
min
0
c4
Duty setting (compressor safety, 0 = OFF, 100 = ON)
C
0
100
min
0
cc
Duration of continuous cycle
C
0
15
hrs
4
c6
Alarm cut-out delay after continuous cycle
C
0
15
hrs
2
DEFROST PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
d0
Defrost (0=electric,1=hot gas,2*=water/electric by time 3*=hot gas by
time)
C
0
3
flag
0
dl
Interval between defrost
F
0
199
hrs
8
dt
Defrost terminate temperature
F
-50
+127
C/ F
4
dP
Max duration of defrost (time protection) if d0=0,1 or defrost time if
d0=2,3
F
1
199
min
30
d4
Defrost on power up (0 = no, 1 = yes)
C
0
1
flag
0
d5
Defrost delay after unit power up or multifunction input
C
0
199
min
0
d6
Display override during defrost (0 = no, 1 = yes)
C
0
1
flag
1
dd
Dripping (drain) time
F
0
15
min
2
d8
Duration of alarm cut-out after defrost and/or opening door
F
0
15
hrs
1
d9
Defrost has priority over compressor protection (0 = no, 1 = yes)
C
0
1
flag
0
d/
Defrost probe reading
F
-
-
C/ F
-
dC
Time basis (0 = hours/minutes, 1 = minutes/seconds) only for dI, dP
C
0
1
flag
0
ALARM PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
A0
Alarm and fan differential (0 = 0.5 deg diff)
C
0
+19
C/ F
0
AL
Low temperature alarm (deviation from set point)
F
0
+127
C/ F
0
AH
High temperature alarm (deviation from set point)
F
0
+127
C/ F
0
Ad
Temperature alarm delay
C
0
199
min
0
A7
External alarm delay (A4 = 2, Multifunction input)
C
0
199
min
0
FAN PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
F0
Management of fans. 0= according to F2,F3 and Fd,
1= Fan regulator (evap temp) F1 = set point
C
0
1
flag
0
F1
Set point for fans
F
-50
+127
C/ F
5
F2
Cycle fans with compressor (0 = no, 1 = yes)
C
0
1
flag
1
F3
Stop fans during defrost (0 = no, 1 = yes)
C
0
1
flag
1
Fd
Fan delay (after dripping time)
F
0
15
min
1
OTHER SETTING
TYPE
MIN
MAX
UNIT
DEF
H0
Address within network
C
0
199
-
1
H1
Alarm relay mode (0 = Alarm On relay energised,
1 = Alarm on relay de-energised.) Different for PJ32S
C
0
1
flag
1
H2
Access Locking (0 = Keypad disabled)
C
0
1
flag
1
H5
Identification code for programming key (set by supervisor)
C
-99
99
-
-