CAREL PROGRAMMING SHEETS
IR32C LOW TEMP REFRIGERATION PARAMETER SUMMARY
PROBE PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
/0
Type of probe (0 = NTC, 1 = PTC) DO NOT CHANGE
C
0
1
-
0
/C
Calibration
F
-20
+20
C/ F
0.0
/2
Measurement stability
C
1
15
-
4
/3
Probe reading speed
C
1
15
-
8
/4
Virtual probe
C
0
100
0
/5
C/ F (0 = C, 1 = F)
C
0
1
flag
0
/6
Decimal point (0 = yes, 1 = no)
C
0
1
flag
0
CONTROL PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
rd
Control differential
F
0.1
+19.9
C/ F
2
r1
Minimum set point allowed
C
-40
r2
C/ F
-40
r2
Maximum set point allowed
C
r1
+199
C/ F
90
r3*
Enable defrost end on time alarm (Ed)
C
0
1
flag
0
r4*
Value to increased set point by when A4 (digital input) = 7
C
0
+20
C/ F
3.0
r5*
Enable min and max temperature logging (0=no, 1=yes)
C
0
1
flag
0
rt*
Interval of min and max temperature logging.
F
0
199
hours
rH*
Max temperature monitored during period rt
F
-50
+90
C/ F
-
rL*
Min temperature monitored during period rt
F
-50
+90
C/ F
-
COMPRESSOR PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
c0
Compressor start-up delay after power up
C
0
15
min
0
c1
Minimum interval between two compressor starts
C
0
15
min
0
c2
Minimum compressor off-time
C
0
15
min
0
c3
Minimum compressor on-time
C
0
15
min
0
c4
Duty setting (compressor safety, 0 = OFF, 100 = ON)
C
0
100
min
0
cc
Duration of continuous cycle
C
0
15
hrs
4
C6
Alarm cut-out delay after continuous cycle
C
0
15
hrs
2
DEFROST PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
d0
Defrost (0=electric,1=hot gas,2*=water/electric by time 3*=hot gas by time)
C
0
3
flag
0
dl
Interval between defrost
F
0
199
hrs
8
dt
Defrost terminate temperature
F
-40
+199
C/ F
4
dP
Max duration of defrost (time protection) if d0=0,1 or defrost time if d0=2,3
F
1
199
min
30
d4
Defrost on power up (0 = no, 1 = yes)
C
0
1
flag
0
d5
Defrost delay after unit power up or multifunction input
C
0
199
min
0
d6
Display override during defrost (0 = no, 1 = yes)
C
0
1
flag
1
dd
Dripping (drain) time
F
0
15
min
2
d8
Duration of alarm cut-out after defrost and/or opening door
F
0
15
hrs
1
d9
Defrost has priority over compressor protection (0 = no, 1 = yes)
C
0
1
flag
0
d/
Defrost probe reading
F
-
-
C/ F
-
dC
Time basis (0 = hours/minutes, 1 = minutes/seconds)
C
0
1
flag
0
ALARM PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
A0
Alarm and fan differential
C
0.1
+20
C/ F
0.2
AL
Low temperature alarm (deviation from set point)
F
0
+199
C/ F
0
AH
High temperature alarm (deviation from set point)
F
0
+199
C/ F
0
Ad
Temperature alarm delay
C
0
199
min
120
A4
Multifunction input one configuration IR32S, Y and C IR32M
C
0
7
-
0
A5
Multifunction input two configuration (IR32_E only)
C
0
7
-
0
A6
Duty setting for external alarm (0 = OFF, 100 = ON)
C
0
100
min
0
A7
External alarm delay (A4 = 2, Multifunction input)
C
0
199
min
0
FAN PARAMETERS
TYPE
MIN
MAX
UNIT
DEF
F0
Management of fans. 0= according to F2,F3 and Fd, 1= Fan regulator
(difference between ambient and evap temp, 2*= Fan regulator (evap temp)
C
0
2
flag
0
F1
Fan turn-off temperature if F0=1 Fans are on when evap temp < (ambient
temp - F1 - A0) if F0=2 Fans are on if evap temp < (set point +F1-A0)
F
0
+20
C/ F
5
F2
Cycle fans with compressor (0 = no, 1 = yes)
C
0
1
flag
1
F3
Stop fans during defrost (0 = no, 1 = yes)
C
0
1
flag
1
Fd
Fan delay (after dripping time)
F
0
15
min
3
OTHER SETTING
TYPE
MIN
MAX
UNIT
DEF
H0
Address within network
C
0
15
-
0
H1
Mulitfunction output (0 = Auxillary, 1 = Alarm n.c., 2= Alarm n.o.)
C
0
1
flag
1
H2
Access Locking (Keypad and or IR remote)
C
0
3
-
1
H3
Code to permit remote programming
C
0
199
-
0
H4
Disable alarm buzzer 1= Yes 0= No (IR32_E only)
C
0
1
Flag
0
* Only on controllers with serial number >100,000