User manual

XXXXXX XXXXXXX XXXXXX XXXXXX
Andover Controls
1 of 2
Andover Continuum Software and Firmware Compatibility Matrix
Versions 1.7 through 1.81
Note: ALL Andover Continuum workstations and web.Client Application Servers must be at the exact same software rev.
CyberStation/web.Client Software Version
Last Updated: June 15, 2007 1.7 1.71 1.73 1.74 1.8 1.81
DB Server OS
Win2000 Server (up to SP4),
Win Server 2003 (up to SP1)
Win2000 Svr (SP4),
Win Svr 2003 (SP1), Win Svr 2003 R2
Win2000 Svr (SP4),
Win Svr 2003 (SP2),Win Svr 2003 R2 (SP2)
SQL Version
MS SQL 2000
1
(up to SP4)
Standard & Enterprise Editions
MS SQL 2000 (up to SP4), MS SQL 2005 (SP2)
Standard & Enterprise Editions
CyberStation PC OS
Win2000 Pro (up to SP4),
Win XP Pro (up to SP2)
.NET Framework v1.1
2
Win2000 Pro (SP4), Win Svr 2000 (SP4),
Win XP Pro (SP2), Win Svr 2003 (SP1),
Win Svr 2003 R2
.NET Framework v2.0
Win2000 Pro (SP4)
7
, Win2000 Svr (SP4)
7
,
Win XP Pro (SP2), Win Svr 2003 (SP2),
Win Svr 2003 R2 (SP2)
.NET v2.0 & .NET v3.0 (Video Only)
LAN
Configuration
web.Client Server OS
Win2000 Pro (up to SP4),
Win XP Pro (up to SP2)
(both up to 2 connections)
Win2000 Server (up to SP4),
Win Server 2003 (up to SP1)
(both up to 25 connections)
.NET Framework v1.1
2
Win2000 Pro (SP4), Win XP Pro (SP2)
(both up to 2 connections)
Win2000 Svr (SP4), WinSvr 2003 (SP1),
Win Svr 2003 R2
(both up to 25 connections)
.NET Framework v2.0
Win2000 Pro (SP4)
7
, Win XP Pro (SP2)
(both up to 2 connections)
Win2000 Svr (SP4)
7
, WinSvr 2003 (SP2),
Win Svr 2003 R2 (SP2)
(both up to 25 connections)
.NET v2.0 & .NET v3.0 (Video Only)
SQL Version MSDE 2000 (up to SP4)
CyberStation SU
(Cyber / DB Server OS)
Win2000 Pro (up to SP4),
Win XP Pro (up to SP2)
.NET Framework v1.1
2
Win2000 Pro (SP4), Win Svr 2000 (SP4),
Win XP Pro (SP2), Win Svr 2003 (SP1),
Win Svr 2003 R2
.NET Framework v2.0
Win2000 Pro (SP4)
7
, Win2000 Svr (SP4)
7
,
Win XP Pro (SP2), Win Svr 2003 (SP2),
Win Svr 2003 R2 (SP2)
.NET v2.0 & .NET v3.0 (Video Only)
Single User
Configuration
web.Client SU
(CyberStation, web.Client Server,
& DB Server OS)
Win2000 Pro (up to SP4),
Win XP Pro (up to SP2),
Win2000 Svr (up to SP4),
Win Svr 2003
(all up to 2 connections)
.NET Framework v1.1
2
Win2000 Pro (SP4), Win2000 Svr (SP4),
Win XP Pro (SP2), Win Svr 2003 (SP1),
Win Svr 2003 R2
(all up to 2 connections)
.NET Framework v2.0
Win2000 Pro (SP4)
7
, Win2000 Svr (SP4)
7
,
Win XP Pro (SP2), Win Svr 2003 (SP2),
Win Svr 2003 R2 (SP2)
(all up to 2 connections)
.NET v2.0 & .NET 3.0 (Video Only)
web.Client: Browser PC OS
Win NT 4.0, Win2000 Pro,
Win2000 Svr, Win XP Pro,
Win Svr 2003
.NET Framework v1.1
2
Win2000 Pro (SP4), Win2000 Svr (SP4),
Win XP Pro (SP2), Win Svr 2003 (SP1),
Win Svr 2003 R2
.NET Framework v2.0
Win2000 Pro (SP4)
7
, Win2000 Svr (SP4)
7
,
Win XP Pro (SP2), Win Svr 2003 (SP2),
Win Svr 2003 R2 (SP2)
.NET v2.0 & .NET v3.0 (Video Only)
web.Client: Browser
2
MS IE 6.0 SP1 MS IE 6.0 SP1, MS IE 7.0
Compatible Firmware Versions
NetController II 2.0
ACX Series (5720/5740) 1.0
CX Controllers 1.5x
CX 9702 1.x
bCX1-CR-INF (Infinet) 1.0, 1.1
3
1.0, 1.1, 1.2
4
i2 Controllers (Infinet) 3.x (3.3 to use xPUI4 Expansion module)
Exceptions:
i2608, i2624, i2804, i2814,
i2885, i2887
3.x
i2865-V, i2866-V, i2885-V
3.5
i2 Controllers-WL
(Wireless Only Infinet)
N/A 3.5
Infinet Controllers 1.4 or greater
Exceptions:
ACX 700 1.5x
ACX 780 1.5x
DCX 250 2.16
LSX 280 Not supported.
bCX1-R, bCX1-CR (BACnet) 4.3 4.3, 4.4, 4.5
5
b4920 4.2
b3 Controllers (BACnet) 4.3 4.3, 4.4, 4.5
Exceptions:
b3865-V, b3866-V, b3885-V 4.5
6
4.5
b3 Controllers-WL
(Wireless Only BACnet)
N/A 4.5
5 v4.5 required on bCX1-R/bCX1-CR to set comm. port for Wireless. 1 MS SQL 2000 Standard and Enterprise (English) Editions supported. SQL Server 2000
Personal Edition is not supported. Please use MSDE 2000 for standalone installations. 6
2 .NET Framework 2.0 is not supported.
BACnet schedules are not compatible for versions below v1.73; only Infinity
schedules are supported.
3 Requires CyberStation/web.Client 1.73 to use firmware’s new features.
7 v1.81 Video Features are not supported on Win2000 Pro or Win2000 Svr.
4 v1.2 required on bCX1-CR-INF to set comm. port for Wireless.
Note: Only the bCX1 supports xPBA4 and xPBD4 Expansion Modules. For xPUI4 support, i2 controllers must be at version 3.3 firmware and b3 controllers must be at
least at version 4.3 firmware.
The information on this chart is furnished for informational purposes only, is subject to change without notice, and should not be construed as a commitment by TAC.
Continuum Compatibility Matrix
XXXXXX XXXXXXX XXXXXX XXXXXXContinuum Compatibility Matrix
Compatibility Matrix-1