User manual

Andover Continuum
BACnet Controllers-12
BACnet
BACnet
b3 xP Expansion I/O Modules
TheBACnet(b3)“plug-in”expansionmodulesprovideaconvenient,lowcost,andflexible
meanstoaddadditionalinputandoutputpointstoContinuum’sdistributedapplication
controllers. Up to two modules (max.) plus a remote mounted (3m max.) display module can be
powereddirectlyfromanyBACnetController,maximum180mAofpoweravailable.Anexternal
power supply can NOT be used to add additional modules.
•Onlythefollowingcontrollerscanaccommodateb3modules:
b3920,b3810,b3814,b3850,b3853,bCX1-CRandACX
•IP20protection
•CEapproved
Technical Specifications
Dimensions: 82mm (H) x 180mm (W) x 40mm (D)
Module Description Contact Power
Rating Consumption
Digital Inputs
xPD18 8digitalinputsfordrycontacts,whichmay 0-5V,140Hz 50mA
also be configured as 140Hz counter inputs
Analogue Outputs
xPAO2 2analogueoutputs,2positionpotentiometer 0-10V,0-20mA 80mA
with no software feedback
xPAO4 4analogueoutputs,2positionpotentiometer 0-10V,0-20mA 120mA
with no software feedback
Digital Outputs
xPDO2 2digitalFormC(SPDT)Relayoutputs, 24VAC/30VDC 60mA
0.1secforPWMcontrol @3A
xPDO4 4digitalFormC(SPDT)Relayoutputs, 24VAC/30VDC 100mA
0.1secforPWMcontrol @3A
xPUI4 4 universal inputs 24VAC/30VDC 125mA
•Range0-5.115VDC @3A
•Temp-34°Cto+110°C
•Counter4Hz
•Supervisedanddigital
Bi-directional Models
xPBD4 3 universal inputs 24VAC/30VDC 125mA
•1UI/140Hzcounter @3A
•4digitalformC(SPDT)Relayoutputs
xPBA4 3 universal inputs 24VAC/30VDC 60mA
•1UI/140Hzcounter @3A
•
4 analogue outputs 0-10VDC (no 0-20mA) with overrides
Local Display Module
xPDisplay 4linesx16char,remotemountable@max.3m N/A 60mA
b3 DI8 Digital Input Module xPDI8
b3 AO2 Analogue Output Module xPAO2
b3 AO4 Analogue Output Module xPAO4
b3 DO2 Digital Output Module xPDO2
b3 DO4 Digital Output Module xPDO4
b3 Universal Input Module xPUI4
b3 Local Display Module (900mm cable) xP-Display
b3 Local Display Module (3m cable) xP-Display-10
4UI/4DO* Expansion Module xPBD4
4UI/4AO* Expansion Module xPBA4
*bCX1-CR-XXonly
Expansion Modules b3 xP
Wireless BACnet Field Bus