User manual

Andover Continuum
Infinet Controllers-16
Infinet
Infinet
i2865-V/i2866-V VAV Controller
TheInfinetII(i2)865-Vand866-Vareunique,lowcostVAVboxcontrollersthatcome
equipped with a built-in damper actuator to streamline hardware installation and reduce
commissioningtime.FreelyprogrammableusingPlainEnglishlanguage,thesestand-alone
controllersarecapableofmonitoring,controlling,schedulingandloggingmodularsystems.
Service and Smart Sensor ports are provided. Up to 254 controllers can be networked on one CX
masterusingContinuum’struepeer-to-peerInfinetnetwork.
•4Universalinputs
•1Airflowsensor
•3FormAtriac-basedoutputs
•1Integrateddamperactuator
•
1Roomsensorinput,whichsupportsContinuum’sSmartSensor
•CompatiblewithbothContinuumCyberStationandInfinitySX8000
•CEapproved
Thei2866-Vmodelisidenticaltothei2865-V,withtheexceptionthatitalsooffers2analogue
outputstocontrolreheatvalves,lightingballastcontrol,positionfeedback,etc.
Technical Specifications
Power: 24VAC,50/60Hz@10VA
OperatingRange: 0°Cto+49°C10-95%RH(non-condensing)
Dimensions: 142mm (H) x 227mm (W) x 62mm (D)
Battery: Replaceable,non-rechargeablelithiumbatteryproviding5years
accumulated power failure back-up
Memory: 128KBRAM,1MBFLASH
Inputs/Outputs
Universal Input:
Supervised,0-5VDCor0-20mA,Temperature(-34°Cto+110°C),
digital counter (4Hz)
Airflow Sensor Input: 0-500Pa
RoomSensorInput: 0°Cto+41°C
FormATriac-basedOutput: SPST24VAC@0.5A(minimum30mA),0.1secforPWMcontrol
Analogue Output (i2866 only): 0-10VDC,5mAmaximum
Damper Actuator:
3.95Nmtorque,acceptsshafts6.35mm-15.9mm(1/4”-5/8”)diameter
A separate isolation transformer must be used for each controller. On Infinity systems the master
controller must be Revision 2.16 or greater.
i2865-V VAV Controller i2865-V
i2866-V VAV Controller i2866-V
Terminal Controllers i2865-V/866-V
Terminal Controller i2867