User manual
Andover Continuum
Infinet Controllers-14
Infinet
Infinet
i2810 Series Local Controllers
TheInfinetII(i2)810isastand-alone,freelyprogrammable(usingPlainEnglishlanguage),
microprocessor-basedlocalcontrollerforDDCcontrol.Capableofmonitoring,controlling,
schedulingandloggingmodularsystems.Thei2810offersthesamefeaturesasthei2800,plus
anI/Oexpansionport,built-inoverridesformanualcontrolofeachoutput,andanoptional
display with keypad for local information control (to be connected to I/O expansion port). Up to 
254controllerscanbenetworkedononeCXmasterusingContinuum’struepeer-to-peerInfinet
network.
•8Universalinputs
•1Roomsensorinput,whichsupportsContinuum’sSmartSensor
•8or4DigitalFormCrelay-basedoutputswithoverrides
•4Analogueoutputswithoverrides
•I/Oexpansionport
•Removableterminalblocks
•Localserviceport
•Realtimeclock
•CompatiblewithbothContinuumCyberStationandInfinitySX8000(i2810only)
•CEapproved
Technical Specifications
Power: 24VAC,50/60Hz@25VAor12-28VDC
OperatingRange: 0°Cto+49°C10-95%RH(non-condensing)
Dimensions:  227mm (H) x 184mm (W) x 54mm (D)
Battery: Replaceable,non-rechargeablelithiumbatteryproviding5years
  accumulated power failure back-up
Memory: 256KBRAM,256KBFLASH
Inputs/Outputs
Universal Input (12 bit): 
Supervised,0-5VDCor0-20mA,Temperature(-34°Cto+110°C),
  digital counter (4Hz)
RoomSensorInput: 0°Cto+41°C
FormCRelay-basedOutput: SPDT24VAC/30VDC@3A,0.1secforPWMcontrol
Analogue Output (8 bit):  0-10VDC
  Universal  Room  Form C  Analogue  I/O  Local  Part 
  Inputs  Sensor  Relay  Outputs  Expansion  Service  Number 
    Input  Outputs    Port  Port 
i2810  8  1  8  -  3  3  i2810
i2814  8  1  4  4  3  3  i2814
Optional
Remote LCD Display - with Keypad (max. distance 3m)  xP-Display
Local Controllers i2810
Terminal Controller i2850 Series