User manual

Andover Continuum
Infinet
Andover Continuum
Infinet Controllers-11
Infinet Infinet
CX9702 AccessController
Designedforsmall,unmanned,orremotesites,theCX9702AccessControllerprovides
networked,electronicaccesscontrol,temperaturecontrol,andalarmmonitoringinasingle,cost-
effectivecontroller.Afullystand-alonedevice,theCX9702controlstwodoors,monitorsfour
supervisedalarmcontactsandfouruniversalalarminputs,andincludestwodigitaloutputsfor
controlofHVACequipment.Throughitson-boardInfinetfieldbus,thesystemcanbeexpanded
toincludeDDCtemperaturecontrol,lightingcontrol,oradditionalmonitoringwithuptofour
stand-alone Infinet controllers.
TheCX9702formspartofanintegratedContinuumFacilityManagementSystem,and
ismonitoredandcontrolledthroughContinuumCyberStationoperatorworkstations,or
Continuum’sweb-basedcompanion,web.Client.Throughdynamic,graphicaldisplays,users
cananalysesystemalarmsandliveconditions,andcanchangesetpoints,alarmthresholds,and
operatingmodesinstantaneously.Cardaccessrecordscanbeedited,privilegesgranted,and
event history analysed to maintain the highest levels of security. An interface to digital video
recording is easily accomplished so that any alarm seen by the CX9702 will cause the correct
camerato“pop-up”totheoperator,andtorecordtheeventforfuturecall-up.
•
Single,EconomicalSolutionforSmall,Unmanned,orRemoteTelecomSites,Providing:
•AlarmMonitoring
•AccessControl
•TemperatureControl
•NativeTCP/IPCommunicationsforEasyNetworkConnectivity
•MonitorTemperature,Humidity,Fire,PowerwithUniversalInputs
•
SNMPCompatible–AllowsAlarmstobeSenttoThirdpartyNetworkManagementSystems
•Supportsweb.Client,Continuum’sWeb-BasedUserInterface
•ExpansionviaContinuum’sInfinetDistributedControllers
•PowerandUPSProvidedforLocks,Readers,Peripherals–SavesInstallationTime
•TotalPointCount:8Inputs,2ReaderInputs,4Outputs
Technical Specifications
Power: 115/230VAC,50/60Hz,115VAconsumption
Peripheral Power:
30W,5V/12V/24V(includedinconsumptiontotal),forreadersandlocks
Overload Protection:
Fusedwith1.5A3AGfuse,1500volttransformerisolation.MOVprotected.
Battery:
Qty1,12V/7.0AHrlead-acidbattery(includedwithenclosurebundles)
Memory: SDRAM: 32MB; FLASH: 4MB
Storage: 200,000CardRecords,with2,000Events
Software Compatibility: CyberStation 1.53 or greater
Inputs/Outputs
Card Reader Type:
SupportsWiegandswipeandproximityreaders,andkeypadsthatsupport
the Wiegand 8-bit burst format. Also supports ABA mag stripe readers.
Card Reader Power:
5V@120mA,12V@180mA,fused,jumper-selectablepercontroller
DoorStrikeRelayOutputs: 2FormCrelays,nooverrideswitches.Usableasgeneralpurpose
digital outputs.
Door Strike Power:
12V@1A,24V@300mAperoutput,fused,jumper-selectableper
controller.Powercanbeinterruptedbyremovingajumper.
DigitalRelayOutputs: 2FormCrelays,withlocaloverrideswitches
Output Indication: LEDs
RelayContactRating: 3A@24VAC;3A@30VDC
CX9702 AccessController CX9702
2readerinputs,8inputs,4DO,10/100bTopenclass
CX9702 AccessController CX9702-4
2readerinputs,8inputs,4DO,10/100bT4Infinetnodes,openclass
XXXXXX XXXXXXX XXXXXX XXXXXX
Network Master Controller CX9702 AccessController