User manual
Andover Continuum
Infinet Controllers-6
Infinet
Infinet
Continuum CX9900 Central Processing Unit (CPU)
The Continuum CX9900 CPU provides monitoring and control of both Continuum I/O modules
and Infinet distributed controllers. Flash memory allows easy on-line software upgrades and is
freely programmable using Plain English programming. The CX9900 connects the high speed
Ethernetnetworktolocalnetworks.QuickreleasefastenersenableDINrailmountingwithout
the need for tools.
•ACC-LONRS-485,andACC-LONFTT-10Aprotocoloptions
•TwistedPair(10BaseT)orFibreOptic(10BaseF)&Ethernetconnectionoptions
•4programmableportsforusewithInfinet,userterminals,printers,modemsand
thirdpartyprotocols
•LEDsforstatus&communication
•Powerconsumptionis10watts@24VDCmax
•Mathco-processorincludedwhenNetControllerisconfiguredwith8MBRAM
•Webserveroptionenabledasstandard.
•Whenusedinaccesscontrolsystems:
4MBRAMModules-5000personnelrecordsforsecurity
8MBRAMModules-78000personnelrecordsforsecurity
Note:
AllNetControllersareTCP/IP.CEApproved.
Description ACC-LON RS-485 Modules A
CC-LON FTT Modules
Part Number Part Number
No Infinet Ports, 2 Comms ports (Port 1 RS-232. Port 3 RS-232):
4MBRAM,16I/OModules* 4M-16I/0-T 4M-16I/O-T-FT
8MB RAM 32 I/O Modules* 8M-32I/0-T 8M-32I/0-T-FT
32 I/O Modules, 4 Comms ports (Port 1 RS-485 or RS-232, Port 2 RS-485, Port 3 RS-232, Port 4 RS-485):
4MBRAM,4Infinetnodelimit 4M-4-T 4M-4-T-FT
4MBRAM,8Infinetnodelimit 4M-8-T 4M-8-T-FT
4MBRAM,32Infinetnodelimit 4M-32-T 4M-32-T-FT
4MBRAM,64Infinetnodelimit 4M-64-T 4M-64-T-FT
8MBRAM,4Infinetnodelimit 8M-4-T 8M-4-T-FT
8MBRAM,8Infinetnodelimit 8M-8-T 8M-8-T-FT
8MBRAM,32Infinetnodelimit 8M-32-T 8M-32-T-FT
8MBRAM,64Infinetnodelimit 8M-64-T 8M-64-T-FT
8MBRAM,127Infinetnodelimit 8M-127-T 8M-127-T-FT
8MBRAM,254Infinetnodelimit 8M-254-T 8M-254-T-FT
*CannotbeupgradedtosupportInfinetfieldbus
XDriver Option
TheCX9900supportstheuseofTAC’sthirdpartycommunicationinterfacescalled
XDrivers.
XDrivers are written in binary format and require that the controller be purchased with this
feature enabled on one or more specified communication ports. The communication port should
be selected according to the protocol type of the XDriver required (RS-485 or RS-232). Ethernet
XDriverscommunicateviatheEthernetport,buttheyrequireanRScommunicationporttobe
allocated. This port cannot be used for other purposes. The CX9900 can support a maximum of
2 XDrivers.
Network Master Controller CX9900 NetController-CPU
NetControllers I & II I/O Modules