User manual
Andover Continuum
Infinet
Andover Continuum
Infinet Controllers-5
Infinet Infinet
NetController II CPU Module
TheAndoverContinuumNetControllerIIisaredesignedversionoftheNetController,ahigh-
powered Central Processing Unit (CPU) module and network manager for the Andover Continuum
intelligentbuildingsystem.Withits128MBDDRSDRAM,32MBflash,andfourprogrammable
communicationsports(includinganinterfacetoTAC’sInfinetdistributedcontrollers),the
NetController II provides a total solution for facility-wide network communications and information
management.OfthetotalDDRSDRAMmemory,12MBisallocatedforapplicationandrun-time
data and 48 MB for personnel records.
The NetController II is compatible with Andover Continuum CyberStation software version 1.8 and
higher,andincludesnewfeaturessuchasnetworksecurity,conditionlevel,arealockdown,andemail.
•NativeEthernetIPNetworkController
•
Powerful,modularCPUboardformonitoringandcontrolofbothAndoverContinuum
I/OModulesandInfinetdistributedcontrollers
•High-speednetworking–4millionnodesonEthernet
•
Fourprogrammablecomm.portsforflexibleinterconnectivityandthirdpartycommunications
•Programmablebatterybackupprovideschoiceofshutdownoptions
•Flashforeasyonlinesoftwareupdates
•AndoverPlainEnglishlanguagesimplifiesprogramming
•DINrailmountingandslide-togetherconnectorsforeasyinstallation
•BackwardcompatiblewithTAC’sInfinityhardware
•
SecureEthernetcommunicationswithIPsec/IKEEncryptionandhardwareacceleration
•Easyconfigurationusingembeddedconfigurationwebpages
•SupportforAreaLockdownandCondition“Threat”Levelbasedaccessrights
•Supportforupto32WirelessInfinetcontrollers
Technical Specifications
Power: 24VAC,50/60Hz,12-28VDCauto-sensing
OperationEnvironment: 0°Cto+49°C,10-95%RH(non-condensing)
Dimensions: 152.4mm (H) x 222.3mm (W) x 63.5mm (D)
Battery:
Sealedrechargeable,batteriesprovide60minutes@35Wattspower
consumption full UPS; 7 day DDRSDRAM and real-time clock. Expandable
I/O Bus: Direct connection of up to 32 Continuum I/O modules
NetController ll
Continuum 1.8 or higher is required. NetController II part numbers define the options
required,asillustratedbelow.
Character Position Options Description
1st-4th NC2- All NetController ll part numbers start with “NC2-”
5th F F for FTT-10A Free topology I/O bus interface
R R for RS485 I/O Bus Interface
6th - 6th character is always “-”
7th - 9th 000 Number of Infinet nodes supported.
008 Note: Zeros are included in node counts to take up 3 character spaces
032
064
127
254
10th H H for High Encryption
0 0 for no Encryption
11th X X for XDriver Support
0 0 for no XDriver Support
Bydefault,XDriveroptionenablesComm1andEthernetlevelXDriver.
Contact TAC for a different configuration.
12th M M for Modem
0 0 for no Modem
13th A
A for Advanced Alarming. (includes both SNMP & Redundant Alarming)
0 0 for no Alarming options
14th C C for Critical Security Features (includes Condition “Threat” Level)
0 0 for no Critical Security features
15th 0 15th character is always “0”
Examples.
NC2-R-00000M000 NetCll,RS485,0nodes,Modem
NC2-F-0320X0A00 NetCll,FTT-10A,32Nodes,XDriverEnabled,AdvancedAlarming
NC2-R-254HXMAC0 NetCll,RS485,254nodes,HighEncryption,XDriverenabled,
Modem,AdvancedAlarming&CriticalSecurity
Network Master Controller NetController II
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
NetController II part numbers
C 2 - -N
0