User Guide

Installation Specications
- 8 -
4"
the unit footprint
Concrete Pad
must extend
18" outside
45.00°
2 1/2" Min.
18" outside the unit footprint
Concrete Pad must extend
8"
4"
Top View
Rebar
Finished Grade
Rebar
CONCRETE SLAB DETAIL FOR TRAFFIC LOADING
(INTERIOR OR EXTERIOR)
Elevation View
(Connecting pipe and fittings by others)
For unit details see specification sheet for selected unit
SIDE VIEW DETAIL
(INTERIOR OR EXTERIOR)
EXCAVATION AND
BACKFILL DETAIL
DIMENSIONS
72”
Maximum
height
Native soil
Concrete slab
Crushed aggregate
material approximately
3/4" size rock, pea gravel
or sand
6” Min. base crushed
aggregate material
approx. 3/4" size rock,
pea gravel or sand
95 proctor.
unit (by others)
Clean out to grade
Flow
on outlet pipe of each
tee (414155BC)
2-Way cleanout
tee (414155BC)
2-Way cleanout
mechnical joint
coupling (by others)
Standard 4”
mechnical joints
coupling (by others)
Standard 4”
on inlet pipe of each
Clean out to grade
unit (by others)
Flow
72”
Maximum
height
50”
26”
22”
14
29”
79”
32”
39.5”
59”
43”
Risers to grade
4075A04 4075A04T
DATE: MAR, 2015
REV: 0
MATL:
PE
DESCRIPTION:
DWG BY: L.S.
DWG NUMBER: 001
Canplas Industries Ltd.
500 Veterans Drive, Box 1800
Barrie, Ontario, Canada L4M 4V3
1-800-461-5300
Canplas LLC
11402 East 53rd Ave., Suite 200
Denver, Colorado, U.S.A. 80239
1-888-461-5307
www.canplas.com
Made in Canada
Endura XL grease interceptors are rated and supplied with an internal flow control system already in place.
They do not require an external flow control system or air intake vent unless specified by local code requirements
or being operated as a PDI G-101 installation. Endura XL grease interceptors are only to be installed in the
manner and for the application shown. Consult local codes for separate trapping requirements, cleanout locations
and additional installation instructions. Full instructional information supplied with every interceptor.
NOTES:
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANPLAS INDUSTRIES. ANY REPRODUCTION IN PART
OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANPLAS INDUSTRIES IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL - © Canplas Industries 2015
Endura® XL - INTERIOR or EXTERIOR BELOW GRADE INSTALLATION INSTRUCTIONS
BELOW GRADE INSTALLATION INSTRUCTIONS
1. EXCAVATION
1.1 Install the Endura ® XL unit(s) as close as possible to xtures being serviced, ideally within 25ft of
developed pipe run from the last xture to the inlet of the interceptor.
1.2 Width and length of excavation shall be minimum 12” greater than the tank dimensions on all sides.
1.3 Depth of excavation shall be at least 6” deeper than tank bottom.
1.4 IMPORTANT: Maximum burial depth 6ft (72”) measured from the air balance channel (EnduraXL Logo)
to nished grade/oor level. Riser extensions available (40100AX35) - (see below).
1.5 Set the tank on well-packed crushed aggregate material approximately 3/4” size rock, pea gravel or
sand. When setting Endura® XL units they must be level laterally and longitudinally.
1.6 Endura® XL tanks are specically designed to resist bouyancy in high water table conditions. Additional
anchoring may however be necessary as determined by the specifying engineer. Tie-down locations are
incorporated to the tank and can be used in conjunction with coated stainless steel cable and an
applicable anchor method based on subsoil. Specific requirements to be determined by specifying engineer.
2. BACKFILLING & FINISHED CONCRETE SLAB (TRAFFIC LOAD RATED)
Endura® XL is supplied standard with trac rated covers designed in accordance with
AASHTO 304 – H20 (16,000lbs) and approved to CSA B481.0 Class ‘S’ -20˚F to +100˚F (-29˚C to +38˚C)
2.1 Preparation of sub grade per local jurisdictional recommendations.
2.2 Stabilize and compact sub grade to 95% proctor per Excavation information above.
2.3 Fill tank with water (to discharge level) to prevent movement during backlling process and to resist
backll load.
2.4 Before backlling and pouring of slab, install riser(s) (as necessary) and cover assembly to suit nished
oor/grade level.
2.5 Backll using crushed aggregate material approximately 3/4” size rock, pea gravel or sand.
2.6 Place minimum 6” aggregate base beneath poured structural slab. Aggregate should be 3/4” size rock or
pea shingle.
2.7 Thickness of concrete around cover to be determined by specifying engineer. If trac loading is required
refer to local specifying engineer recommendations and/or local code requirements. Note: Concrete slab
dimensions shown are for illustration purposes only.
2.8 Concrete to be 28 day compressive strength to 4000 PSI. Reinforcement with No.4 rebar (1/2”) grade 60
steel per ASTM A615: connected with tie wire. Rebar to be 2½” from edge of concrete. Rebar spacing
12” grid. 4” spacing around access openings.
3. PIPING CONNECTIONS
3.1
All Endura® XL Grease Interceptors are manufactured with no hub connections. Threaded connections are
available from your Canplas distributor suxing the product code with ‘T’ – i.e. 40100A04T
3.2 Locally approved mechanical joint (MJ) couplings are used to connect the inlet and outlet piping to the
tank. This allows transition to dierent piping materials as required.
3.3 Make system piping connections using locally approved MJ couplings installing to manufacturer’s
instructions. Review all eld-made connections for leaks before backlling begins. Isolate the tank from
the system both up and down stream and ll tank with water, submersing the inlet and outlet fully
below the water level. DO NOT PRESSURE TEST – Risk of serious Injury or Death.
3.4 DO NOT decrease pipe diameter across the unit (i.e. 4 inch inlet, 3 inch outlet). If the piping system
needs to be resized, use appropriate mechanical joint reducers consistent with the direction of ow and
installed in compliance with local code.
4 EXTENSION RISERS (Optional)
4.1 Endura® XL Extension Risers provide a maximum of 35” extension per riser. Based on maximum
installation depth up to a maximum of 72” depth of burial can achieved (see 1.4 above), adding
Extension Risers (or part thereof) during installation. Risers are cut to length on site to suit installation.
4.2 Remove cover from interceptor. Set aside for use at nished grade/oor level.
4.3 Secure riser to tank (frame remains in place) using xings provided. Ensure seal is correctly located.
4.4 Secure the 1-1/2” adapter tting supplied with the Extension Kit to the thread on the top of the handle
mechanism. Cut and extend a length of 1½” DWV pipe per instructions supplied.
4.5 For custom riser length - measure from tank frame to nished grade/oor level. Subtract 1½”. Cut
cleanly by hand or mechanical means using guide rings molded into the riser to give clean straight cut.
Note - Horizontal surface of cover will be 0.5” above nished oor/grade.
4.6 Fit riser seal provided over the cut edge of the riser and locate frame (supplied) over the seal making
sure it is fully seated. Secure with lag screws provided using the pre-drilled locations in frame.
4.7 Repeat process for additional riser if/as required.
4.8 With frame installed and veried at the correct height, pass the handle extension support over the 1½”
DWV and secure the support to the frame with the screw provided. Solvent weld a 1½” vent tee on top
of the pipe to act as a handle.
4.9 Re-t the original cover(s) provided with the interceptor.