Specication:
Sample specication clause.
Contractor shall install a Canplas Endura® XL Hydromechanical Grease Interceptor (HGI), Part No. 40100A04
q
, 40100A04T
q
,
4075A04
q
, 4075A04T
q
(Indicate as applicable), and rated to 100GPM
q
75GPM
q
(Indicate as Applicable) independently third-
party certied to the current version of PDI G-101, ASME A112.14.3 and CSA B481.1. Approved alternate is permissible providing written
compliance to the following is provided and validated.
Where an internal ow control is desirable and acceptable to the Authority Having Jurisdiction (AHJ), the interceptor shall be rated and
approved to ASME A112.14.3 Type C. The ow control shall be accessible for cleaning and inspection up to the maximum burial depth of
72” regardless of the application and when requiring Riser Extension, the installing contractor will extend the opening device according
to manufacturers published instructions. The outlet system will provide facility for connections to be made perpendicular to the inlet
connection. Connection formats will be compliant with requirements of AHJ and the performance standards identied above. Contractor
shall provide mechanical joint connectors or requisite materials to connect the grease interceptor to the drainage system, additionally
making adequate provision for management of food debris and solids.
Interceptor shall be furnished with two (2) trac rated access covers, maximizing internal visibility for inspection and maintenance when
removed. These covers shall be capable of withstanding a proof load of 20,000lbs, being qualied for application at temperatures from
-20˚F to +100˚F (-29˚C to +38˚C). The cover will be mechanically secured when operational.
The interceptor tank shall be constructed with seemless engineering thermoplastics, evaluated and approved to the material
performance requirements of CSA B481.0
The interceptor shall additionally; operate with an air-balanced environment to equalize variation in internal pressures being controlled
and maintained with an appropriately sized air balance means; be supported by a Lifetime Warranty against manufacturing defect.
For approved Plumbing & Drainage Institute (PDI) installation, an accessible ow control 40442100A
q
, 4044275A
q
40442100AT
q
, 4044275AT
q
(Indicate as applicable) with molded orice and removable access cap will be installed upstream of
the interceptor, being vented and installed according to manufactures instructions and the currently published version of PDI G-101
Interceptor will be located within 25ft developed pipe run of the last connected appliance for operational compliance. Where applicable
a secondary ow control will be employed in installations where there is greater than 8ft of vertical elevation between the kitchen
discharge appliances and the interceptor inlet.
Air Intake can be connected to building
vent system or be independently to the
atmosphere based on local code.
• Average Eciency % (ASME A112.14.3) 98% 99%
• Operating Temperature Capabilities
(Intermittent discharge)
160˚F
(71˚C)
160˚F
(71˚C)
• Cover Load Capacity
(Third Party Tested)
20,000 lbs
(9072 kgs)
20,000 lbs
(9072 kgs)
• Unit Weight Capacity (Empty) 233 lbs
(106 kgs)
283 lbs
(128 kgs)
• Liquid Capacity 158 gal
(598 L)
257 gal
(973 L)
• Connection size (mechanical) 4” 4”
XL75 XL100
• Flow Control
• Flow Control
Pipe by
others
• Air Intake Tee
• Air Intake Tee
Connection
Iron Pipe Size
(Solvent weld)
4” h x h
A 6.13”
(155.7mm)
B 6.84”
(173.7mm)
C -
4” h x h
3.19”
(81mm)
5.04”
(128mm)
2.72”
(69.1mm)
Capacities
External Flow
Control Dimensions
• Part Number
Add Sux “T” For FPT Connections
4075A04
(4075A04T)
40100A04
(40100A04T)
Flow Rate (GPM) 75 100
Flow Rate (L/Sec) 4.74 6.3
CAPACITY - Lbs (MIN) 150 200
CAPACITY - Kg (MIN) 68 91
CAPACITY - Lbs (Actual - ASME A112.14.3) 559 1058
CAPACITY - Kg (Actual - ASME A112.14.3) 253 480
• Solids Capacity lbs (Kg) estimated 260lbs (118kg)
45 Gallons
350lbs (159kg)
60 Gallons
For full CAD, BIM Models
and 3 Part Master Format
Specs visit www.arcat.com