Instruction manual
12 | Cannon Fitzroy / Canterbury Inbuilt
FITZROY & CANTERBURY INBUILT FLUEING
Flue Adaptor
(supplied as standard)
The flue must be fixed in place.
Ø100mm flue 
Heater
Install heater 
onto a solid, 
leveled base.
Roof cladding
500mm between top of 
cowl and nearest part of 
roof. (Also refer to AS/ 
NZS 5601.1)
Flue cowl 
approved to 
AG604/
AS4566
Flue clamp
Flashing
Fit two lengths of vertical flue (1.8m) before fitting 
any 45° bends. If bends are used, fit inside of flue 
pipe. Use no more than two 45° bends in the total 
flue run and maintain at least 250mm of straight 
flue pipe between the bends.
FIG 7 This diagram is to be used as a general guide only.
carried out by an authorised person. 
Refer to Australian Standard Gas 
Installations AS/NZS 5601.1.
Installing a flue on the shorter wall may 
subject it to down draughts or reverse 
air flows through the heater which can 
be difficult to find a solution to. Always 
adopt correct flue design practices. 
Refer to Australian Standard Gas 
Installation AS/NZS 5601.1 for ‘location 
of flue terminal’. 
The heater has been tested and should 
operate satisfactorily with an optimum 
flue length of 4.5 meters.
Exceeding this length may affect the 
stability of the flame pattern and the 
operation of the heater. Contact our 
Technical Support Department if any 
further advice is required.