Specifications

InstallationandOperationManual(REVH) PVI6500/PVI7500

48
5Troubleshooting
5.1 Diagnos isandanalysingdata
Identifyingandresolvingfaults
ThePVI65007500isfittedwithaselfdiagnosticsystem,whichcanrecognizethemajorityofpossiblefaultsandshowtheseon
thedisplay.ThisallowstheoperatortorapidlyidentifypossibleproblemsinthesolarinverterorPVsystem.Pleaserefertothe
LCDsection(4)forathorough
explanationoffaultcodes,modes,etc.
GroundFault:
Ifasignificant ground fault occurs inthe PV array or wiring,theGFDI fuse (locatedinthe wiringbox) may beblown.If it is,
locate and repair the ground fault and only then replace the fuse with BussmannKLKD1 (1 Amp, 600VDC). Call the Solectria
Renewablescustomer
servicehotlineforassistancewithlocatingaDCgroundfaultinthearrayorconduits.
IftheGFDIdetectsagroundfault,theGroundFaultLEDwilllightandthe“fault”willbedisplayed.
WeakSunlightCondition:
Operationin weaksunlight,(forexampleearlyinthemorning,whenovercastorwhensnowiscoveringmostorallofthePV
array)cancausetheinvertertogothroughacycleoftryingtostartandrestartseveraltimes.Thiscanoccurifthearrayreaches
260V(strikevoltage)
butthereisnearlynopoweravailable.
5.2 ExplanationsofErrorMessages
Intheeventofafault,theinverterwillstopfeedingtheACvoltagetothebuilding/utilityanddisplaytheerrormessageonthe
LCD.Qualifiedservicepersonnelshalldotheanalysis,measurement,anddebugthesystem.Itisrecommendedtoanalyzethe
fault condition(s) by referring to the table below
and then remove the fault condition(s) in order to return the inverter to a
normalstateandcontinuetofeedACpowertotheutility.PleasecontactSolectriaRenewablescustomerservicehotlineifthe
errormessagedoesnotclear.
WARNING: Certain trouble shooting steps may require work on energized and exposed circuits, only
qualified personnel should perform these tasks. Please use Personal Protective Gear when measuring
voltageintheinverter.
ErrorMessageTable
ErrorMessage Description PossibleSolutions
GridNA
NoACvoltageisdetected.
VerifyACvoltagedisconnectison
‐VerifyACcircuitbreakeris
on/operational
‐VerifyandmeasureACvoltagepresent
inInverterdisconnect
‐ContactinstallingcompanyorSolectria
Renewables
DriftFac
Islandingisdetected.
VerifyACvoltagepresentandcorrect
inInverterdisconnect
‐ContactinstallingcompanyorSolectria
Renewables
VacH
TheACvoltageofutilityisabovetheupper
limit.
VerifysettingforS201iscorrectfor
thegridvoltageapplied
‐MeasuretheACvoltageandcompare
tothevoltageontheinverterdisplay
‐ContactSolectriaRenewablesfor