User`s guide

Section 2
MultiMux Operation and Installation
9
2.8 Enclosure Installation
The MicroMux can be attached to any surface with 4 mounting 6-32 screws.
The placement of the mounting holes is depicted in the illustration below.
H1
L1
4H1
4L1
4H2
VW
Gage
4L2
CHANNEL
4
MicroMux4
3H1
3L1
3H2
VW
Gage
3L2
CHANNEL
3
2H1
2L1
2H2
VW
Gage
2L2
CHANNEL
2
1H1
1L1
1H2
VW
Gage
CHANNEL
1
S
12V
G
CLK
VW
Gage
EN
COMMON
H2
L2
www.canarysystems.com
Made in the U.S.A.
CURRENT LIMIT: 2A 30VDC MAX
S
SHIELD
1L2
6 inches
2 inches
6 inches = 15.2cm
2 inches = 5.1cm
Note: The Micromux can be installed
upside down, vertically, or horizontally.
2.9 Input Protection
The MicroMux is equipped with lightning protection components on the control signals. As a result, care
must be exercised in the installation to maximize their effectiveness. Specifically, an effective earth
ground must be attached to the MicroMux shield (S) for proper protection. Most Vibrating wire instruments
also have lightning protection components.
The Enable and Clock inputs can be connected to 12 volts directly without damaging the MicroMux. The
connections to the datalogger should be disconnected and insulated from contacting other electrical
connections. The 12V tolerant inputs allow the MicroMux to be field tested without the need for a
datalogger connection. The enable can be wired to the 12V input while the clock input can be touched to
12V. This action will cause the MicroMux to step channels for each touch to 12 volts.