User manual
TVS user manual Testing settings and equipment
41
When the TVS is in stage override mode, it does not operate the equipment
according to the measured temperature.
The TVS does not exit test mode on its own. When you are finished testing,
press
Back until the control exits test mode.
To use stage override mode
1. Press Program until test displays and then press Select.
The display shows 28, the first item in the Test menu.
2. Press Select.
The display shows st91, the first item in the Stage override
submenu.
3. Press Up or Down until the stage you want to test displays, for
example ALA for the alarm relay and then press Select.
The display shows the current setting.
4. Press Up or Down to adjust the setting and then press Select.
The control returns to the Stage override menu.
5. Repeat steps 3 to 4 for each stage you want to test.
6. To return to the Main menu, press Back twice. To return to the
Main display, press Back three times.
Using temperature override mode,
parameter 29
Temperature override mode is for testing the TVS configuration and
settings. It allows you to test the settings by simulating the temperature. Instead of adjusting the
output of a variable stage or state of a relay, you adjust the "test temperature".
As you increase or decrease the test temperature, all stages and relays operate according to their
programmed settings and the test temperature, giving you an idea of how your system performs over
a full range of temperatures.
When the TVS is in temperature override mode, it operates according to the test
temperature, not according to the temperature measured by the probe.
The TVS does not exit test mode automatically. When you are finished testing,
press
Back until the control exits test mode.