27
3. Press Up or Down to choose the configuration you want and then press Select.
The control returns to the Configuration menu.
4. To return to the Main menu, press Back once. To return to the Main display, press Back twice.
Configuring the relay stage, parameter 17
The TVS has one relay stage you can configure as one of the following options.
Off: the relay is always open (OFF).
On: the relay is always closed (ON). You can use this configuration as an override.
Cool: the relay controls a cooling element and is on when the temperature is above the set point.
Heat: the relay controls a heating element and is on when the temperature is below the set point.
If you need to connect more cooling elements than you have relays available,
and you are not using both variable stages, you can use an available variable
stage as an ON/OFF stage (for 120/230 VAC-powered equipment only). For
more information, read
Programming variable stages, parameters 2 to 9 on page
33.
Use the Variable and relay stages configuration worksheet on page 57 when
configuring relays.
Default: COOL
To configure the relay stage
1. Press Program until (0Nf displays and then press Select.
The display shows 13, the first item in the Configuration menu.
2. Press Up until17displays and then press Select.
The display shows the current configuration.
3. Press Up or Down until you reach the option you want and then
press Select.
The control returns to the Configuration menu.
4. To return to the Main menu, press Back once. To return to the
Main display, press Back twice.
(0Nf
*
0ff