Chapter 3: Configuring your TVS Phason
24
Configuring the main control functions
Before configuring the variable and relay stages, configure the main control functions. Main control
functions include:
Temperature units
Frequency
Hysteresis
Selecting the temperature units, parameter 13
Your TVS can display temperatures in either degrees Fahrenheit (°F) or degrees Celsius (°C), but
not both at the same time.
Default: Fahrenheit
To select the temperature unit
1. Press Program until (0Nf displays and then press Select.
The display shows 13, the first item in the Configuration menu.
2. Press Select.
The display shows the current temperature unit.
3. Press Up or Down to toggle between °F and °C and then press
Select.
The control returns to the Configuration menu.
4. To return to the Main menu, press Back once. To return to the
Main display, press
Back twice.
Selecting the operating frequency, parameter 14
In North America, utility companies supply power at 60 Hz. In some areas of the world, such as
Europe, power is supplied 50 Hz.
Default: 60 Hz
C
ONF
°f