Product Manual
51
SV01N_13418587 EN/DE/ES/FR/IT/PT
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Segment #12
P765
Segment #12
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
P766
Segment #12
Accel/Decel Time
20.0 0.0 {sec} 3600.0
P767
Segment #12
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P768
Segment #12
Digital Output State
0
Value set in P768 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P769
Segment #12 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #13
P770
Segment #13
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
P771
Segment #13
Accel/Decel Time
20.0 0.0 {sec} 3600.0
P772
Segment #13
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P773
Segment #13
Digital Output State
0
Value set in P773 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P774
Segment #13 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #14
P775
Segment #14
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
P776
Segment #14
Accel/Decel Time
20.0 0.0 {sec} 3600.0
P777
Segment #14
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P778
Segment #14
Digital Output State
0
Value set in P778 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P779
Segment #14 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10