Product Manual

39
SV01N_13418587 EN/DE/ES/FR/IT/PT
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
p207
Proportional Gain 5.0 0.0 {%} 1000.0 Used to tune the PID loop:
• Increase P207 until system becomes unstable,
then decrease P207 by 10-15%
• Next, increase P208 until feedback matches
setpoint
• If required, increase P209 to compensate for
sudden changes in feedback
p208
Integral Gain 0.0 0.0 {s} 20.0
p209
Derivative Gain 0.0 0.0 {s} 20.0
NOTE
• DerivativeGainisverysensitivetonoiseonthefeedbacksignal.Usewithcare.
• DerivativeGainisnotnormallyrequiredinpumpandfanapplications
p210
PID Setpoint Ramp 20.0 0.0 {s} 100.0 • time of setpoint change from P204 to P205
or vice versa.
• Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
p214
Minimum Alarm 0.0 P204 P205 Use with P140, P142 = 18...23
P215
Maximum Alarm 0.0 P204 P205
P231
Preset PID Setpoint #1 0.0 P204 P205 TB-13A activated; P121 = 3 and P200 = 1 or 2
P232
Preset PID Setpoint #2 0.0 P204 P205 TB-13B activated; P122 = 3 and P200 = 1 or 2
P233
Preset PID Setpoint #3 0.0 P204 P205 TB-13C activated; P123 = 3 and P200 = 1 or 2
P234
(2)
Preset PID Setpoint #4 0.0 P204 P205 TB-13D activated; P124 = 3 and P200 = 1 or 2
P240
Sleep Threshold 0.0 0.0 {Hz} 500.0 • If drive speed < P240 for longer than P241,
output frequency = 0.0 Hz; drive display =
SLP
• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again when speed
command is above P240
• P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242 or when the PID loop
requires a speed above P240.
P241
Sleep Delay 30.0 0.0 {s} 300.0
P242
Sleep Bandwidth 0.0 0.0 B
max
Where: B
max
= |(P205 - P204)|
P243
Feedback Sleep
Entry Threshold
0.0 P204 P205 Active only when P244 = 1 or 2
P244
Sleep Entry Mode 0 0 Enter SLEEP if Drive Speed <P240 For time longer than P241
1 Enter SLEEP if Feedback >P243 For time longer than P241 or same as Sel 0
2 Enter SLEEP if Feedback <P243 For time longer than P241 or same as Sel 0
P245
Sleep Entry Stop
Type
0 0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
P246
Feedback Recovery
from Sleep Threshold
0.0 P204 P205 Active only when P247 = 1 or 2
P247
Sleep Recovery
Mode
0 0 Recovery if Speed Setpoint > P240
or if PID feedback differs from setpoint
by more than P242
1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246
(2) Parameter applicable to SMV models 15HP (11kW) and higher.