Product Manual
32
SV01N_13418587 EN/DE/ES/FR/IT/PT
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
p140
Relay Output
TB-16, 17
0 0 None Disables the output
1 Run Energizes when the drive is running
2 Reverse Energizes when reverse rotation is active
3 Fault De-energizes when the drive trips, or power is
removed
4 Inverse Fault Energizes when the drive trips
5 Fault Lockout P110 = 3...6: De-energizes if all restart attempts
fail
6 At Speed Energizes when output frequency = commanded
frequency
7 Above Preset Speed #6 Energizes when output frequency > P136
8 Current Limit Energizes when motor current = P171
9 Follower Loss (4-20 mA) Energizes when 4-20 mA signal is < P164
10 Loss of Load Energizes when motor load drops below P145;
Refer to P146 also
11 Local Keypad Control Active
Energizes when the selected source is active for
start control
12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference Active Energizes when P101 reference is active
16 Auto Reference Active Energizes when Auto Reference is activated using
TB-13 input; refer to P121...P124
17 Sleep Mode Active Refer to P240...P242
18 PID Feedback < Min. Alarm Energizes when PID feedback signal < P214
19 Inverse PID Feedback < Min. Alarm De-energizes when PID feedback signal < P214
20 PID Feedback > Max Alarm Energizes when PID feedback signal > P215
21 Inverse PID Feedback > Max Alarm De-energizes when PID feedback signal > P215
22 PID Feedback within
Min/Max Alarm range
Energizes when PID feedback signal is within the
Min/Max Alarm range; refer to P214, P215
23 PID Feedback outside
Min/Max Alarm range
Energizes when PID feedback signal is outside the
Min/Max Alarm range; refer to P214, P215
24 Reserved
25 Network Controlled SMV models < 15HP (11kW) require an optional
communication module (refer to the network
module documentation).
26 Loss of 0-10V Input Energizes when 0-10V signal is < P158
27 Sequencer Controlled State set in individual sequencer segments
28 Sequencer Active
29 Sequencer Suspended
30 Sequence Done End Sequence
31 Output Frequency = 0.0Hz Output inactive
p142
TB-14 Output 0 0...23 (same as P140)
24 Dynamic Braking For use with Dynamic Braking option
25...31 (same as P140)