Specification

Owners Manual
8
Installation: Electrical requirements
Canadian Spa Company requires that the electrical installation of your
hot tub is carried out by a professionally licensed electrician and that
all local electrical and building codes are adhered to.
Access to the electrical pack can be found by removing the panel
directly below the topside control.
CONNECTING HOT TUB TO GFCI AND MAIN PANEL:
• All hot tubs must be wired with the appropriate sized wiring.
Failure to do so will cause equipment damage and will not be
covered by your warranty
All hot tubs must be protected with a appropriately sized GFCI
in the consumer panel. Have your electrician verify using
the diagram below
ITEMS NEEDED TO HELP COMPLETE ELECTRICAL CONNECTION:
GFCI Breaker, electrical cable (check length and width for amperage
and distance), cable gland, clips.
IMPORTANT: The electrical wiring of this spa must meet the
requirements of any applicable local codes. The electrical circuit
must be installed by a qualified electrician and approved by a local
building/electrical inspection authority.
1. This spa must be permanently connected (hard wired) to the
power supply. No plug-in connections or extension cords are to
be used in conjunction with the operation of the spa.
Supplying power to the spa which is not in accordance with
these instructions will void both the independent testing agency
listing and the manufacturer’s warranty.
2. The power supplied to this spa must be a dedicated circuit with
no other appliances or lights sharing the power provided by the
circuit.
3. To determine the proper wire size, see Electrical Requirements
section.
a) Wire size must be appropriate as per local codes.
b) All wiring must be copper to ensure proper connections. Do
not use aluminum wire. Using aluminum wire will void the
manufacturer’s warranty.
4. Although not required, a suitably rated isolator switch is
recommended for accessibility.
5. The electrical circuit supplied for the spa must include a suitable
Ground Fault (GFCI) having a rated residual operating
current not exceeding 30 mA.
IMPORTANT: For supply connections, use conductors sized on the
basis of amperage but rated for 75°C (167°F).
6. An GFCI breaker must be used in order for the spa to function
properly.
7. To gain access to the spa’s power terminal block, remove the
screws to the access panel located under the Topside Console.
Remove the cover to the spa controller.
8. Feed the supply power cable through the side of the spa or from
underneath the unit. Use the appropriate cable gland to secure
the power supply.
9 Connect the wires, colour to colour on the terminal block.
TIGHTEN SECURELY (all wires must be connected securely or
damage could result).
10. After connecting your the electrical connection close the spa
control box cover and replace the spa access panels.
3. Hot tub Control box
1. Consumer Panel
(GFCI Protected)
2. Outside isolation
switch
Electrical Installation NORTH AMERICA 60HZ
Spa Model Voltage requirement Minimum GFCI Size Minimum AWG
Yukon Plug & Play 110V N/A N/A
Quebec Plug & Play 110V N/A N/A
Winnipeg Plug & Play 110V N/A N/A
Toronto 220V 50A #6
Thunder Bay 220V 50A #6
Niagara 220V 50A #6
Victoria 220V 50A #6
Alberta 220V 50A #6
Halifax 220V 50A #6
Montreal 220V 50A #6
St Lawrence 13’ Sport Pool 220V 60A #6
St Lawrence 16’ Swim Spa 220V 60A #6
Refer to this table for the
electrical requirements of your
Canadian Spa hot tub.
Do not use an electrical
extension cord to install any
Canadian Spa hot tub.
The GFCI (ground fault circuit
interrupter) must be installed
according to the pictures below.
ELECTRICAL WIRING PLAN (NORTH AMERICA)