Use and Care Manual

16 | EM...M
EN
Installation, operating and maintenance instructions
Our devices require little maintenance when operated properly.
e following work should be performed at regular intervals, in accordance with health and safety regulations:
Check the operation of the control system and safety devices.
Check electrical connections and wiring for damage.
Remove any dirt from the fan impeller or impellers and from inside the fan housing in order to prevent any unba-
lance or reduction in output.
Do not use aggressive or easily flammable products for cleaning (impellers/housing).
Preferably only water (not flowing water) or mild soapsuds should be used.
e impeller should be cleaned with a cloth or brush.
Never use a high-pressure cleaner.
Balancing clips must not be moved or removed.
e impeller and fittings must not be damaged in any way.
Before putting the unit back into operation after maintenance and servicing work, carry out a visual inspection as
described in section 11. and 12.
13.1. Checklist Maintenance and Service
Description check interval
Triggering device monthly
Fan
Check fan for function and operational readiness (test run at least 15 minutes) every 6 months
Check fan for function and operational readiness (test run at least 1 hour) yearly
Check for dirt, damage, corrosion and fastening every 6 months
Function-preserving cleaning every 6 months
Check impeller rotation direction yearly
Check flexible connections for leaks yearly
Check impeller for imbalance yearly
Check protective device for function yearly
Motor
Check externally for dirt, damage, corrosion and fastening every 6 months
Function-preserving cleaning yearly
Check bearing for noise yearly
Check terminals for tight fit yearly
Measure the voltage yearly
14. LIFETIME AND DISPOSAL
14.1. Product life
e motors are equipped with maintenance-free, permanently lubricated ball bearings. Under normal operating condi-
tions, the expected lifetime is about 30,000 operating hours.
e information given here depends strongly on the respective field of application as well as the environmental condi-
tions. We recommend replacing these fans after reaching about 30,000 operating hours or 5 years.